Manual

Enter
Y
our Final Sensorconfiguration V
alues Here
Configure the QDC Module's
Inputs and Outputs
Chapter 3
3-11
Complete the procedure for configuring the QDC module to match its
sensors by spanning them over their intended range with the machine in
operation. Here we describe how you determine:
clamp position sensor values
ejector position sensor values
clamp pressure sensor values
ejector pressure sensor values
In the procedures that follow, measure and record:
minimum and maximum positions
corresponding signal values
minimum and maximum pressures
corresponding signal values
After determining these values, write them down on Worksheet 3-E.
Important: You must complete this configuration before proceeding to
any other chapters on module configuration.
Worksheet 3E
Final
Sensorconfiguration V
alues
Input Control Word ProSet 600 Addr. Value Description Units
1 MCC37 N41:33 0 Minimum Ejector Position Ejector Axis Measured from zero
1
MCC38 N41:34 Maximum Ejector Position Ejector Axis Measured from zero
1
MCC39 N41:35 Analog Signal @ Min Ejector Position Input Signal Range
2
MCC40 N41:36 Analog Signal @ Max Ejector Position Input Signal Range
2
2 MCC45 N41:41 0 Minimum Ejector Pressure Ejector Pressure
3
MCC46 N41:42 Maximum Ejector Pressure Ejector Pressure
3
MCC47 N41:43 Analog Signal @ Min Ejector Pressure Input Signal Range
2
MCC48 N41:44 Analog Signal @ Max Ejector Pressure Input Signal Range
2
3 MCC23 N41:19 0 Minimum Clamp Position Clamp Axis Measured from zero
1
MCC24 N41:20 Maximum Clamp Position Clamp Axis Measured from zero
1
MCC25 N41:21 Analog Signal @ Min Clamp Position Input Signal Range
2
MCC26 N41:22 Analog Signal @ Max Clamp Position Input Signal Range
2
4 MCC31 N41:27 0 Minimum Clamp Pressure Clamp Pressure
3
MCC32 N41:28 Maximum Clamp Pressure Clamp Pressure
3
MCC33 N41:29 Analog Signal @ Min Clamp Pressure Input Signal Range
2
MCC34 N41:30 Analog Signal @ Max Clamp Pressure Input Signal Range
2
1
Incremental Distance
2
Input Signal Range
3
Pressure
00.00
to 99.99 Inches
00.00 to 10.00V dc or
0000 to 9999 PSI
000.0 to 999.9 Millimeters
01.00 to 05.00V dc or
000.0 to 999.9 Bar
04.00 to 20.00MADC
Complete your Sensor
Configuration