User Manual
Chapter
8
8-1
Load Initial Profile Values
This chapter describes how to load profile setpoints for inject and clamp
operations. You determine initial values and enter setpoints into PLC-5
data table for the following profiles:
Clamp Close Profile (CPC)
Injection Profile (IPC)
Pack/Hold Profile (HPC)
Plastication Profile (PPC)
Clamp Open Profile (OPC)
Important: This chapter continues the procedure for loading information
into the QDC module. Complete chapter 7 before starting this chapter.
The following table lists command blocks and corresponding worksheets
for recording your initial values that you download to the QDC module.
To configure the QDC module
with this profile block
See this
Worksheet
On
Page
Clamp Close Profile Block (CPC) Worksheet 8A 8-2
Injection Profile Command Block (IPC) Worksheet 8B 8-10
Pack/Hold Profile Command Block (HPC) Worksheet 8C 8-18
Plastication Profile Command Block (PPC) Worksheet 8D 8-24
Clamp Open Profile Block (OPC) Worksheet 8E 8-30
Take a moment now to browse through the first worksheet.
Notice that it contains two parts:
control words for selecting parameters by setting bits
block of data words for recording initial profile values
Also notice that many parameters repeat within the profile block.
For example: segments 1-11 for velocity setpoints
Because many parameters repeat within a worksheet, we present each
worksheet followed by text telling you how to determine initial values.
Complete one worksheet before going to the next. This differs from the
procedure in chapter 7.
Chapter
Objectives
Use These W
orksheets