Load Initial Configuration Values
Chapter 7
7-32
Table 7.A
Setoutput
V
alues for Unselected V
alves
If the unselected
valve controls:
and the unselected
valve type is:
and during profile,
valve action is:
and during profile,
you require:
Then Enter:
Pressure Unidirectional Direct acting Maximum Pressure 9999
Pressure Unidirectional Direct acting Medium Pressure 7500 to
5000
Pressure Unidirectional Direct acting Low Pressure 5000 to
2500
Pressure Unidirectional Direct acting Minimum Pressure 0
Pressure Unidirectional Reverse acting Maximum Pressure 0
Pressure Unidirectional Reverse acting Medium Pressure 2500 to
5000
Pressure Unidirectional Reverse acting Low Pressure 5000 to
7500
Pressure Unidirectional Reverse acting Minimum Pressure 9999
Flow Unidirectional Direct acting Maximum Flow 9999
Flow Unidirectional Direct acting Medium Flow 7500 to
5000
Flow Unidirectional Direct acting Low Flow 5000 to
2500
Flow Unidirectional Direct acting Minimum Flow 0
Flow Unidirectional Reverse acting Maximum Flow 0
Flow Unidirectional Reverse acting Medium Flow 2500 to
5000
Flow Unidirectional Reverse acting Low Flow 5000 to
7500
Flow Unidirectional Reverse acting Minimum Flow 9999
Flow Bidirectional Direct acting Maximum Flow 9999
Flow Bidirectional Direct acting Medium Flow 8750 to
7500
Flow Bidirectional Direct acting Low Flow 7500 to
6250
Flow Bidirectional Direct acting Minimum Flow 5000
Flow Bidirectional Reverse acting Maximum Flow 0
Flow Bidirectional Reverse acting Medium Flow 1250 to
2500
Flow Bidirectional Reverse acting Low Flow 2500 to
3750
Flow Bidirectional Reverse acting Minimum Flow 5000
Important: Valve spanning procedures in chapter 9 require unselected
valves be driven at signal levels representative of a normal production run.
We discuss process considerations that impend changing these values in
chapter 10. Changing these values may require you to re-span your valves.
Enter all set-output values for unselected valves in worksheets 7-A – 7-L.