Instruction Manual

Load Initial Configuration Values
Chapter 7
7-16
Table 7.A
Setoutput
Setpoints for Unselected V
alves
If the unselected
valve controls
and the unselected
valve type is
and during profile,
valve action is
and during profile,
you require
Then enter
Pressure Unidirectional Direct acting Maximum pressure 9999
Pressure Unidirectional Direct acting Medium pressure 7500 to 5000
Pressure Unidirectional Direct acting Low pressure 5000 to 2500
Pressure Unidirectional Direct acting Minimum pressure 0
Pressure Unidirectional Reverse acting Maximum pressure 0
Pressure Unidirectional Reverse acting Medium pressure 2500 to 5000
Pressure Unidirectional Reverse acting Low pressure 5000 to 7500
Flow Unidirectional Reverse acting Minimum pressure 9999
Flow Unidirectional Direct acting Maximum flow 9999
Flow Unidirectional Direct acting Medium flow 7500 to 5000
Flow Unidirectional Direct acting Low flow 5000 to 2500
Flow Unidirectional Direct acting Minimum flow 0
Flow Unidirectional Reverse acting Maximum flow 0
Flow Unidirectional Reverse acting Medium flow 2500 to 5000
Flow Unidirectional Reverse acting Low flow 5000 to 7500
Flow Unidirectional Reverse acting Minimum flow 9999
Flow Bidirectional Direct acting Maximum flow 9999
Flow Bidirectional Direct acting Medium flow 8750 to 7500
Flow Bidirectional Direct acting Low flow 7500 to 6250
Flow Bidirectional Direct acting Minimum flow 5000
Flow Bidirectional Reverse acting Maximum flow 0
Flow Bidirectional Reverse acting Medium flow 1250 to 2500
Flow Bidirectional Reverse acting Low flow 2500 to 3750
Flow Bidirectional Reverse acting Minimum flow 5000
Important: Valve spanning procedures in chapter 9 require unselected
valves be driven at signal levels representative of a normal production run.
We discuss process considerations that impend changing these values in
chapter 10. Changing these values may require you to re-span your valves.
Record all set-output values for unselected valves in worksheets 7.A – 7.D.