Chapter 5
513
Continuous Stroking
From figure
5.7
Both voting processors allow
continuous stroking regardless of
releasing RUN buttons.
Has an operator pressed a
STOPONTOP button?
Has the PLC transferred a
stopontop command?
Has a barrier guard opened?
Both voting processors trip triac
power to stop the shaft. A trip
condition message is displayed.
WARNING: If the shaft coasts
past its neartop position while
braking, the brake is faulty and
hazardous. Repair it immediately.
NOTE: The press strokes continuously until an operator presses a STOPONTOP button, the
PLC transfers a stopontop command, or barrier guard opens.
12267
Yes
No
No
Yes
Yes
The stroke continues until the
shaft reaches the neartop
position
Is the shaft in the neartop
position?
Both voting processors
deenergize their solenoid triacs
to stop the shaft in its neartop
position.
Yes
No