Instruction Manual
Programming
Chapter 3
311
Figure 3.5
Master
Control W
ord W01
1
0
W01
1
0
1
1
LOOP 1
2 LOOPS
EXPANDED
STANDARD
CALIB BINARY
BCD
BINARY
BCD
SP
SOFT
FAULT
RESET
DIAG
LOOP
TIME
LOAD
00
VERIFY
CODE
ENTER
SET
OUTPUT 2
SET
OUTPUT 1
MANUAL
REQUEST
W01 B07 1=Report diagnostics in W60
0=Report loop time in W60
W01 B06 1=Initiates load/enter sequence
0=Sequence not initiated
W01 B05 Must be set to 0
W01 B04 Must be set to 0
W01 B03 1=Completes the load/enter sequence
0=Loop constants remain in buffer
W01 B02 1=Set Analog Output 2 (W12)
0=Use algorithm output
W01 B01 1=Set Analog Output 1 (W05)
0=Use algorithm output
W01 B00 1=Contact closure oneshot
0=Off; resets oneshot
W01 B17 Must be set to 1
W01 B16 Must be set to 1
W01 B15 1=Loop 1 only
0=Both Loop 1 and Loop 2
W01 B14 1=Expanded loop features
0=Standard loop features
W01 B13 1=Calibration
0=Normal Operation
W01 B12 1=Binary format for words W05, W09, W10,
W12, W16, W17, W63, W64, W66, W70,
W71, and W73
0=BCD format
W01 B11 1=Binary format for the set point W06 (W13)
0=BCD
W01 B10 1=Soft Fault Reset
0=Remain in Soft Fault
11108
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00