Instruction Manual
Summary Word and Bit Tables
Appendix D
D12
Table D.G
Alarm Word W58
Bits Title Status
B17,B16
Block identifier
will be 0
B15
Dynamic block error
0=no error
1=programming error
B14
Loop block error
0=no error
1=programming error
B13 Power-up
0=Dynamic block is received.
1=Memory is clear
, ready for LE sequence.
B12 Ready 0=normal
1=Load portion of LE sequence is complete, ready for enter portion.
B11
Loss of
+
15V DC
0=normal
1=loss of
+
15V DC
B10
Soft fault mode
0=normal mode
1=soft fault mode
B07 thru
B00
Future use
will be 0
Table D.H
Status Monitor Byte
Bit No.
Title Status
B07,B06 Precondition
0=Byte is valid.
1=invalid byte
B05 Precondition
0=Byte is invalid
1=valid byte
B04 Alarm
0=no alarm condition
1=An alarm condition is reported in loop status word W61(W68).
B03 Power-up
0=Dynamic block is received.
1=Memory is clear
, ready for LE sequence. (SMB B03 mirrors the status of W58
B13).
B02
Loss of input
0=Signal is present
1=loss of analog input or tieback input (under most circumstances)
B01
Loss of +15V DC
0=normal
1=loss of
+
15V DC (SMB B01 mirrors the status of W58 B1
1).
B00
Soft fault mode
0=normal mode
1=soft fault mode (SMB B00 mirrors the status of W58 B10).