Installation Instructions Instruction Manual

AC (120/220V) 16A Power Supply6
Publication
17715.39  December 1995
Mounting the Power Supply Separately
When mounted separately, the power supply may be mounted above
or next to the I/O chassis. It may not be mounted below, since it is
necessary to allow convection cooling of both the power supply and
the I/O chassis. A minimum vertical distance of 6 inches should be
maintained.
1. Mount the power supply vertically, above and within the
specified cable-feet (for your cable) of the D-shell connector on
the I/O chassis.
Allow for a generous bend of the
1771CP2 or 1771CP3 cable to reduce
stress on the connectors mounted on
the chassis and the power supply.
Use the rear mounting flanges on the
power supply to mount it to a panel.
1771P7
15.2cm
(6")
12621I
2. Connect one end of the power cable (ordered separately) to the
D-shell connector located on the bottom of the power supply and
tighten the connector screws.
1771-CP2 or 1771CP3 cable
1771P7
connector screws
12622I