6–4 Calibrating Your Module
&%! ' #
Gain Calibration
Calibrating gain requires that you apply 402.00 ohms across each
input channel.
Normally all inputs are calibrated together. To calibrate the gain of
an input, proceed as follows:
1. Connect 402.00 ohm resistors across each input channel as shown
in Figure 6.2 below.
Figure 6.2
Resistor Location for Gain Calibration
#
%%!
! $$%!#
"% !#
2. Apply power to the module.
3. After the connections stabilize, request the gain calibration by
setting bit 01 in BTW word 15 and sending a block transfer write
(BTW) to the module.
NOTE: Normally, all channels are calibrated simultaneously (bits
10–15 of word 15 are octal 0). To disable calibration on any channel,
set (1) the corresponding bit 10 through 15 of word 15.