Owner's manual

Getting Started with Your ASCII Module
Chapter 2
213
Press [DISPLAY] 1
Results The industrial terminal displays the name and numbers (first 10
characters) that you entered in step 2. For example,
ALLEN 12345 would be displayed as:
POSITION FILE
DA
TA
ASCII Equivalent
001 E010
status word one
002 0000
status word two
003 414C
A L
004 4C45
L E
005 4E20 N
006 3132 1 2
007 3334 3 4
Entering the eleventh character caused the module to transfer the data.
Note the space entered between ALLEN and 12345.
The display of status word one (E010) and status word two (0000)
indicates normal status of the module.
3. Terminate this display by pressing [CANCEL COMMAND], and
return to ladder diagram.
Need Help?
If your display was all zeros, the data did not transfer. You may have
altered the procedure.
Did you enter your program exactly as shown?
Did the module’s CHANNEL ACTIVE LED go on?
Did you perform Procedure P1 before P2?
Did you perform Step 1 in Procedure P2?
Did you perform Step 3 in Procedure P2?