Using I/O Configuration SoftwareE–4
Publication
17716.5.99 - December 1995
In mode(s)Current programming You
scalers for total
(multiply/divide)
enter a multiplier and divisor here, separated by a (/) to have the module report
total counts in units meaningful to your application
(the multiplier must be ≤ the divisor)
RANGE: 032,767 DEFAULT: 1/1 (no scaling)
For example, if 15 counts represent 2 gallons, you could scale counts to gallons by
entering scalers of 2/15.
Scaling affects only the total counts value that the module returns in the BTR.
All programming in the BTW - e.g. rollover value, output ON and OFF values is
still in Hz .
T,
NR
T
rollover value
enter a count value that the totalizer will reset or rollover to 0 at (when the unscaled
count reaches that value, the module sets the overflow status bit in the BTR and
starts counting again from 0)
RANGE: 0-9,999,999 DEFAULT (if you enter 0): 10,000,000
T,
NR
T
tied to outputs
see the output(s) that are currently tied to this input channel (this field is display
only to tie outputs to a different input channel, use the Output Setup screen.
all
reset total see if the Total Reset (BTW word 1, bits 0030) is ON (this field is display only).
T
reset overflow see if the Overflow Reset (BTW word 1, bits 0407) is ON (this field is display only).
T,
NR
T
start prover
see the current settings in the BTW data file (you must make any changes to this
field through a running program on the PLC processor, or by directly setting bits in
the BTW; you can not edit these fields with the I/O Configuration software)
T,
NR
T
prover type, uni
or bidirectional
press (F9) Toggle to select the type of prover you are using in your application
0 = unidirectional 1 = bidirectional.
T,
NR
T
Mode abbreviations:
Totalizer = T
Nonresettable T
otalizer = NRT Highresolution Frequency = HR Direction Sensor = DS