Manual
Replace Your QRC ModuleC–6
Publication
17716.5.99 - December 1995
Connect your I/O devices to the 40-terminal field wiring arm
(cat. no. 1771-WN) shipped with the CFM module. Use the wiring
example on page C–7 for additional assistance on connecting
your devices.
F0 RET
F2 RET
Customer V DC #1 (5 to 40V)
Output 1
10689I
F0 Input
F2 Input
Output 0
Customer
V DC #1 RET (Outputs 0 &1 RET)
Even Numbered T
erminals 240
Odd Numbered T
erminals 139
NEW wiring arm (1771WN)OLD wiring arm (1771WG)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
18322
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
Overspeed
outputs turned on within
1ms of frequency calculation.
(+) Magnetic pickup and shield Channel A
(-) Magnetic pickup
(+) Magnetic pickup and shield Channel B
(-) Magnetic pickup
Overspeed solid state relay Channel A
Overspeed solid state relay Channel B
Solid state relay common
actual wiring runs in this direction
The sensor cable must be shielded. The shield:
• must extend the length of the cable, but be connected only
at the 1771 I/O chassis
• must extend up to the point of termination
Important: The shield should extend to the termination point,
exposing just enough cable to adequately terminate the
inner conductors. Use heat shrink or another suitable
insulation where the wire exits the cable jacket.
Make Connections to the
New Wiring Arm