Replace Your QRC ModuleC–6
Publication
17716.5.99 - December 1995
Connect your I/O devices to the 40-terminal field wiring arm
(cat. no. 1771-WN) shipped with the CFM module. Use the wiring
example on page C–7 for additional assistance on connecting
your devices.
F0 RET
F2 RET
Customer V DC #1 (5 to 40V)
Output 1
10689I
F0 Input
F2 Input
Output 0
Customer
V DC #1 RET (Outputs 0 &1 RET)
Even Numbered T
erminals 240
Odd Numbered T
erminals 139
NEW wiring arm (1771WN)OLD wiring arm (1771WG)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
18322
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
Overspeed
outputs turned on within
1ms of frequency calculation.
(+) Magnetic pickup and shield Channel A
(-) Magnetic pickup
(+) Magnetic pickup and shield Channel B
(-) Magnetic pickup
Overspeed solid state relay Channel A
Overspeed solid state relay Channel B
Solid state relay common
actual wiring runs in this direction
The sensor cable must be shielded. The shield:
must extend the length of the cable, but be connected only
at the 1771 I/O chassis
must extend up to the point of termination
Important: The shield should extend to the termination point,
exposing just enough cable to adequately terminate the
inner conductors. Use heat shrink or another suitable
insulation where the wire exits the cable jacket.
Make Connections to the
New Wiring Arm