Manual

5–5Interpret Module Status and Input Data
Publication
17716.5.99 - December 1995
word 11 (channel 0)
word 20 (channel 1)
word 29 (channel 2)
word 38 (channel 3)
word 10 (channel 0)
word 19 (channel 1)
word 28 (channel 2)
word 37 (channel 3)
word 10 (channel 0)
word 19 (channel 1)
word 28 (channel 2)
word 37 (channel 3)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Acceleration (rate of change of frequency)  the calculated acceleration value (Hz/s).
RANGE: -32,767 to 32,767
all
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Total  the total counts registered by the input channel.
Example: If word 9 = 93 and word 10 = 1234, Total = 93(10,000) + 1,234 = 931,234
RANGE: 0  9,999,999
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
T, NRT
MSD
 ranges from
0999 x 10,000
LSD  ranges from 09,999
word 9 (channel 0)
word 18 (channel 1)
word 27 (channel 2)
word 36 (channel 3)
word 12 (channel 0)
word 21 (channel 1)
word 30 (channel 2)
word 39 (channel 3)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Direction indicates the current detected direction 0 = stopped
of the input pulses in Direction Sensor modes. 1 = clockwise
2 = counterclockwise
DS
word 13 (channel 0)
word 22 (channel 1)
word 31 (channel 2)
word 40 (channel 3)
word 14 (channel 0)
word 23 (channel 1)
word 32 (channel 2)
word 41 (channel 3)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Prover Total Count Value or Store Count Value  when Prover Run Initialize (BTW 1, bits 811) is:
enabled  the value returned is the prover count (intermediate and final run values).
not enabled  the value returned is the last count stored when the Gate input went low to high. These words
are reset to 0 when Prover Run Initialize (BTW 1, bits 811) changes in bit state from a 0 to a 1.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
T, NRT
MSD
 ranges from
0999 x 10,000
LSD  ranges from 09,999
If Bandwidth Limit is:
ON  orientation and frequency can be sensed to
1/Minimum Frequency Sampling Time. Frequencies <
1/Minimum Frequency Sampling Time are reported as stopped.
OFF  direction can be sensed to 0.33Hz and frequencies < 1Hz
are reported as 0.