4–7Configure the CFM Module
Publication
17716.5.99 - December 1995
output on when >=
On
or <
Off
output on while >=
On
and < Off
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output OFF Value the value at which the output turns OFF. all
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
MSD ranges from
0999 x 10,000
LSD ranges from 09,999
12,000 15,000
On Value
Of
f V
alue
12,00015,000
word 47 (channel 0)
word 51 (channel 1)
word 55 (channel 2)
word 59 (channel 3)
word 48 (channel 0)
word 52 (channel 1)
word 56 (channel 2)
word 60 (channel 3)
Prover
Range of Operation
(value of bits in hex)
:
0 =
prover not selected
1 =
prover is not running, but
active
2 =
prover running past the 1st switch in forward leg
3 =
prover is done with forward leg, returning at this time
midrun value (bidirectional only)
4 =
prover is returning on 2nd leg (bidirectional only)
5 =
prover is done with run (BTR word 13/14 contains prover count value)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output ON Value the value at which the output turns ON.
all
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
MSD ranges from
0999 x 10,000
LSD ranges from 09,999
ON
and OFF output values can be triggered by:
Frequency
= 0120,000
Percent of Fullscale
= 032,767 (use LSD word 46, 50, 54, 58
only)
Acceleration
= -32,768 32,767 (use LSD word 46, 50, 54, 58
only)
Total
= 09,999,999
Direction
= 0 (stopped), 1 (clockwise), 2 (counterclockwise)
(use LSD word 46, 50, 54, 58
only)
Overflow
= 0 (output follows
Overflow
bit, BTR words 4 & 5)
Prover Range of Operation
= 05 ON and OFF values must be different
(use LSD word 46, 50, 54, 58
only)
Prover Running
= 0 Output is ON when the prover is actually counting.
unidirectional prover: ON from 25
bidirectional prover: ON from 23 and 45
word 45 (channel 0)
word 49 (channel 1)
word 53 (channel 2)
word 57 (channel 3)
word 46 (channel 0)
word 50 (channel 1)
word 54 (channel 2)
word 58 (channel 3)
Important: When any type of scaling is used (frequency or total),
outputs are always triggered by the actual value not the
scaled value. Outputs triggered by Total turn ON in < 100µs
and turn OFF in < 100µs. All other ON and OFF times
are < 1ms.