4–6 Configure the CFM Module
Publication
17716.5.99 - December 1995
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Total Scaler
➀
Divisor the total value
returned in the BTR is divided by the
specified value.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
T, NRT
Rollover Value the count value that
the totalizer will reset or rollover to 0 at.
T, NRT
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
MSD - ranges from
0999 x 10,000
LSD ranges from 09,999
RANGE: 0 9,999,999
DEFAULT: 0 (which is rollover of 10,000,000)
RANGE: 0 32,767 DEFAULT: 1
Important: The Total Scaler Multiplier must be ≤ Total Scaler Divisor.
See Total Scaler Multiplier.
word 12 (channel 0)
word 22 (channel 1)
word 32 (channel 2)
word 42 (channel 3)
word 13 (channel 0)
word 23 (channel 1)
word 33 (channel 2)
word 43 (channel 3)
word 14 (channel 0)
word 24 (channel 1)
word 34 (channel 2)
word 44 (channel 3)
Important: The Rollover Value must be ≥ (actual frequency x 10ms).
If you are using the prover function, the expected Prover
Total Count Value (BTR words 13/14, 22/23, 31/32, or
40/41) must be < Rollover Value.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Total Scaler
➀
Multiplier the total
value returned in the BTR is multiplied by
the specified value.
T, NRT
word 11 (channel 0)
word 21 (channel 1)
word 31 (channel 2)
word 41 (channel 3)
RANGE: 032,767 DEFAULT: 1
Important: The Total Scaler Multiplier must be ≤ Total Scaler Divisor
.
See Total Scaler Divisor.
➀
When scaling is used, all outputs are still controlled by the actual value not the scaled value.