User Manual Owner's manual

3–17Addressing Modes for Your Remote I/O
+#!*!&%  (+(- 
When using double-slot block-transfer modules:
The left slot of the two corresponding I/O groups must be
empty.
You can place any single-slot I/O module in the right slot
of the two corresponding I/O groups.
When using single-slot block-transfer modules, the corresponding
I/O group must be empty.
The following rules apply when you assign I/O rack numbers:
When you select 1-slot addressing, set switches of switch assembly
S1 to assign the first I/O rack number of the chassis. The remote I/O
adapter module automatically assigns the next higher I/O rack
number to the remaining I/O groups of the chassis.
For example, if you want a 16-slot chassis that you set for 1-slot
addressing to begin with I/O rack number 0, set switches of switch
assembly S1 for I/O rack number 0. The adapter module
automatically assigns I/O rack number 1 to the remaining I/O groups
of the chassis (Figure 3.15).
Figure 3.15
Assigning I/O Rack Numbers with 1Ćslot Addressing

* ),!* ) & ),!* ))$#- 
&% *  ($&*  '*( $&+#
&(  (" %+$(    '*(
+*&$*!##- ))!%)  (" %+$.
( *& *  ($!%!%  (&+' &
*   ))!)
.   ))!) +)!% .)#&* ())!%
 (&+'
+$(
))!%  "
+$(
))!%  "
+$(
01 23 45 67 01 23 45 67
You assign one I/O rack number to eight I/O groups, regardless of
which addressing method you select.
Assigning I/O Rack
Numbers with 1ĆSlot
Addressing