Owner manual
HART Command Data Table Layouts
Appendix A
A-7
Standard Outputs
Integer Word 30 STT Subroutine Status Wordg
Word 31 STT Subroutine Error Code
Word 32 Smart Transmitter Interface Status Word
Word 33 Smart Transmitter Interface Error Code
Word 34 HART ProtocolCommunication Error Code
Word 35 HART Command Response Summary Code
Word 36 HART Field Device Error Code
Commandspecific Outputs
Integer Word 41 Primary Variable Unit Codeg
Word 42 Secondary Variable Unit Code
Word 43 Tertiary Variable Unit Code
Word 44 4th Variable Unit Code
Floatingpoint Word 10 Primary Variable Currentgp
Word 11 Primary Variable
Word 12 Secondary Variable
Word 13 Tertiary Variable
Word 14 4th Variable
Data Table Report PLC-5/25 Addr 31 Data Table File N10:0
Address 0 1 2 3 4 5 6 7 8 9
N10:0 4 6 3 0 16 3 9858 269 12807 0
N10:10 0 0 0 0 0 0 0 0 0 0
N10:20 0 0 0 0 0 0 0 0 0 0
N10:30 4 0 128 0 0 0 0 0 0 0
N10:40 0 32 250 250 250 0 0 0 0 0
N10:50 0 0 0 0 0 0 0 0 0 0
These four integer words are the commandspecific outputs
that contain the unit codes for the variables (see page B5).
These seven integer words are the standard outputs
that contain the status of the communications with
the HART field device. (see page 36).
These four floatingpoint words are commandspecific outputs
that contain the variables from the HART field device.
Data Table Report PLC-5/25 Addr 31 Data Table File F11:0
Address 0 1 2 3 4
F11:0 0 0 0 0 0
F11:5 0 0 0 0 0
F11:10 7.29 20.58 0 0 0
F11:15 0 0 0 0 0
This floatingpoint word is a commandspecific
output that contains the primary variable current.
HART Command 3
Read
Dynamic V
ariables & Primary
V
ariable Current