74 Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Define Indicate this These bit settings
15…1
1
10 9 8 7…
4
3210
Input Range
Select
-10 to +10V dc
0000
0 to 5V dc 0001
0 to 10V dc
0010
4 to 20 mA 0011
1 to 5V dc 0100
0 to 20 mA
0101
Input Data
Select
Raw/Proportional
Counts
000
Engineering Units 0 0 1
Scaled for PID 0 1 0