106 Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Configuration Data File
To select Make these bit settings
1514131211109876543210
Filter Frequency
10 Hz
Not Used
(1)
(1) An attempt to write any nonvalid (spare) bit configuration into any selection field results in a module
configuration error.
110
60 Hz 000
50 Hz
001
250Hz 011
500 Hz 100
1 kHz
101
Open-circuit
Upscale 00
Downscale 01
Hold Last State 10
Zero 11
Temp.
°C 0
°F 1
Input Type
Thermocouple J 0000
Thermocouple K 0001
Thermocouple T 0010
Thermocouple E 0011
Thermocouple R 0100
Thermocouple S 0101
Thermocouple B 0110
Thermocouple N 0111
Thermocouple C 1000
-50…50 mV 1001
-100…100 mV 1010
Data Format
Raw/Proportional
Data
000
Engineering Units 001
Engineering Units x
10
100
Scaled-for-PID 010
Percent Range 011
Enable
Disabled 0
Enabled 1