User Manual
Configuring the Module 3-13
When the Configuration Mode switch is in the “Parameter” position, the
1769-SM1 uses its internal parameters setting to configure the module.
Any configuration data downloaded by the controller will be ignored.
Important: When the Parameter mode is used, the configuration data size
in the controller should be set to “0.” Refer to Controller
Mode on page 3-2 for more information.
Only DPI products (PowerFlex 70, etc.) can utilize this feature since DPI
peripheral devices (HIMs, DriveExplorer with 1203-SSS converter, etc.)
can access the 1769-SM1 directly. Allowing DPI peripherals to change
the configuration settings makes the Parameter mode more flexible and
simpler to use than Controller mode.
Figure 3.15 DriveExplorer Window with Mapped 1769-SM1 Compact I/O Module
Parameter Mode
Table 3.B Module Configuration Data Words in Parameter Mode
Description
CH1
Parameter
CH2
Parameter
CH3
Parameter
I/O Config 7 24 41
Idle Action 9 26 43
Fault Config. Logic Command 10 27 44
Fault Config. Reference 11 28 45
Fault Config Datalink In A1 12 29 46
Fault Config Datalink In A2 13 30 47
Fault Config Datalink In B1 14 31 48
Fault Config Datalink In B2 15 32 49
Fault Config Datalink In C1 16 33 50
Fault Config Datalink In C2 17 34 51
Fault Config Datalink In D1 18 35 52
Fault Config Datalink In D2 19 36 53