User Manual Manual

74 Publication 1769-UM009E-EN-P - August 2009
Chapter 5 Manually Configure the DeviceNet Network
This parameter enables the slave functionality of the scanner, and lets you set
the I/O behavior, with the amount of data to be exchanged. The Slave mode
settings are described in this table.
Advanced Module Settings
Clicking Advanced opens this dialog.
Slave Mode Settings
Connection Format Description
Strobed Not supported by the 1769-SDN scanner module.
Polled Values entered into Rx and Tx parameters define how
much data will be exchanged over the polled connection
that owns the scanner’s slave I/O. Maximum size is 128
bytes.
Change of State / Cyclic Values entered into Rx and Tx parameters define how
much data will be exchanged over the change of state or
cyclic connection that owns the scanner’s slave I/O.
Maximum size is 128 bytes.