User manual

Rockwell Automation Publication 1769-UM011I-EN-P - February 2013 29
Install the 1769-L3x Controllers Chapter 2
Connect the RJ-45 connector of the Ethernet cable to the Ethernet port (top
port) on the controller.
Assign an IP Address
You can set the IP address by using any of these utilities:
Rockwell BOOTP Utility (available with RSLinx and RSLogix 5000
software)
RSLinx software
RSLogix 5000 software
Use BOOTP to Set the IP Address
The BOOTP utility is a standalone program in one of the following directories:
RSLinx Tools directory in the Rockwell Software® program folder on the
Start menu
The utility is automatically installed when you install RSLinx software.
Utils directory on the RSLogix 5000 software installation CD
Follow this procedure to use the BOOTP utility.
1. Start the BOOTP software.
2. Select Tools>Network Settings.
3. Enter the Ethernet mask and gateway.
ATTENTION: Do not plug a DH-485 network cable or a NAP cable into the
Ethernet port. Undesirable behavior or damage to the port may result.
8 ------ NC
7 ------ NC
6 ------ RD-
5 ------ NC
4 ------ NC
3 ------ RD+
2 ------ TD-
1 ------ TD+
8
1
RJ-45