Rockwell Automation Publication 1769-UM011I-EN-P - February 2013 23
Install the 1769-L3x Controllers Chapter 2
3. Use the upper and lower tongue-and-groove slots (B) to secure the
modules together.
4. Move the module back along the tongue-and-groove slots until the bus
connectors line up with each other.
5. Use your fingers or a small screwdriver to push the module’s bus lever back
slightly to clear the positioning tab (C).
6. Move the module’s bus lever fully to the left (D) until it clicks, being sure it
is locked firmly in place.
7. Attach an end-cap terminator (E) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end-cap bus terminator (F).
Mount the System
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow
50 mm (2 in.) of space on all sides, as shown. This provides ventilation and
electrical isolation.
ATTENTION: When attaching the controller, power supply, and I/O modules,
make sure the bus connectors are securely locked together to be sure of proper
electrical connection.
This equipment is not resistant to sunlight or other sources of UV radiation.
ATTENTION: During panel or DIN-rail mounting of all devices, be sure that all
debris (such as metal chips or wire strands) is kept from falling into the
controller. Debris that falls into the controller could cause damage while the
controller is energized.
Bottom
Side
Side
Top
CompactLogix
Controller
Power Supply
Compact I/O Module
End Cap
50 mm
(2 in.)
50 mm
(2 in.)
50
mm
(2 in
.)
50 mm
(2 in.)
Compact I/O Module