Technical data
92 Rockwell Automation Publication 1769-TD006C-EN-P - March 2012
1769 Compact I/O Modules Specifications
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag
automatically resets when within the normal operating range.
(2) Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
(3) Includes offset, gain, nonlinearity, and repeatability error terms.
(4) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(5) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(6) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC
input signal and 20V DC potential above ground).
Table 70 - Environmental Specifications - 1769-OF4VI
Attribute 1769-OF4CI
Temperature, storage -40…85 °C (-40…185 °F)
Temperature, operating 0…60 °C (32…140 °F)
Relative humidity 5…95% noncondensing
Altitude, operating 2000 m (6561 ft)
Vibration, operating 10…500 Hz, 5 g, 0.030 in. peak-to-peak
Shock, operating 30 g, 11 ms panel-mounted (20 g, 11 ms DIN rail-mounted)
Shock, nonoperating 40 g panel-mounted (30 g DIN rail-mounted)
Radiated and conducted emissions
IEC 61000-6-4
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2
4 kV contact
8 kV air
4 kV indirect
Radiated immunity
IEC 61000-4-3
10 V/m, 80…1000 MHz, 80% amplitude modulation
Burst, fast transient
IEC 61000-4-4
2 kV, 5 kHz
Surge immunity
IEC 61000-4-5
1 kV galvanic gun
Conducted immunity
(1)
IEC 61000-4-6
(1) Conducted immunity frequency range may be 150…30 MHz if the Radiated immunity frequency range is 30…1000 MHz.
10V DC, 0.15…80 MHz
Table 71 - Certifications - 1769-OF4VI
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-OF4VI
c-UL C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
UL listed for Class I, Division 2 Group A,B,C,D Hazardous Locations (ANSI/ISA 12.12.01-2007, C-UL under CSA C22.2 No. 213)
CE CE compliant for all applicable directives
C-Tick C-Tick compliant for all applicable directives
AustralianRadiocommunications Act, compliant with:
• • AS/NZS cispr 11; Industrial Enclosure