Technical data
58 Rockwell Automation Publication 1769-TD006C-EN-P - March 2012
1769 Compact I/O Modules Specifications
1769-IT6
Compact Thermocouple/mV input module
Thermocouple Type °C Temperature Range °F Temperature Range
J -210…+1200 °C -346…+2192 °F
K -270…+1370 °C -454…+2498 °F
T -270…+400 °C -454…+752 °F
E -270…+1000 °C -454…+1832 °F
R 0…+1768 °C +32…+3214 °F
S 0…+1768 °C +32…+3214 °F
B +300…+1820 °C +572…+3308 °F
N -210…+1300 °C -346…+2372 °F
C 0…+2315 °C +32…+ 4199 °F
Millivolt Input Type Range
± 50 mV -50…+50 mV
± 100 mV -100…+100 mV
Input
Type
Engineering Units x1 Engineering Units x10 Scaled-for-PID Raw/
Proportional Data
Percent Range
0.1 °C 0.1 °F 1.0 °C 1.0 °F
J -2100…+12000 -3460…+21920 -210…+1200 -346…+2192 0…+16383 -32767…+32767 0…+10000
K -2700… +13700 -4540…+24980 -270…+1370 -454…+2498 0…+16383 -32767…+32767 0…+10000
T -2700…+4000 -4540…+7520 -270…+400 -454…+752 0…+16383 -32767…+32767 0…+10000
E -2700…+10000 -4540…+18320 -270…+1000 -454…+1832 0…+16383 -32767…+32767 0…+10000
R 0…+17680 +320…32140 0…+1768 +32…3214 0…+16383 -32767…+32767 0…+10000
S 0…+17680 +320…32140 0…+1768 +32…3214 0…+16383 -32767…+32767 0…+10000
B +3000…18200 +5720…32767
(1)
(1) Type B and C thermocouples cannot be represented in engineering units x1 (°F) above 3276.7 °F; therefore, it will be treated as an over-range error.
+300…1820 +572…3308 0…+16383 -32767…+32767 0…+10000
N -2100…+13000 -3460… +23720 -210…+1300 -346…+2372 0…+16383 -32767…+32767 0…+10000
C 0…+23150 +320…32767
(1)
0…+2315 +32…4199 0…+16383 -32767…+32767 0…+10000
±50 mV -5000…+5000
(2)
-500…+500
(2)
(2) When millivolts are selected, the temperature setting is ignored. Analog input date is the same for °C or °F selection.
0…+16383 -32767…+32767 0…+10000
±100 mV -10000…10000
(2)
-1000…1000
(2)
0…+16383 -32767…+32767 0…+10000
NC
IN 0+
IN 0-
IN 3+
IN 1 +
IN 3-
IN 1-
IN 4+
IN 2+
IN 4-
IN 2-
IN 5+
IN 5-
NC
+
-
+
-
+
-
CJC 0+
CJC 0-
CJC 1-
CJC 1+
CJC Sensor
Ungrounded
Thermocouple
CJC Sensor
Grounded Thermocouple
Grounded Thermocouple
Within 10V DC