1769 Compact I/O Modules Specifications
Isolation voltage 500V AC or 710V DC for 1 minute (qualification test), group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 281 g (0.62 lb)
Dimensions (HxWxD), approx 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
Module location DIN rail or panel mount
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Power supply distance rating 8 modules
Terminal screw torque 0.68 Nm (6 lbin)
Retaining screw torque 0.46 Nm (4.1 lbin)
Wire size (22…14 AWG) solid
(22…16 AWG) stranded
Wire type Cu-90 °C (194 °F)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 series B (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Product type code 10
Product code 47
Input words 22
Output words 2
Configuration words 98
Enclosure type rating None (open-style)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag
automatically resets when within the normal operating range.
(2) Resolution is dependent upon your filter selection. The maximum resolution is achieved with either the 50 or 60 Hz filter selected.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC
input signal and 20V DC potential above ground).
(4) For proper operation, both the plus and minus input terminals must be within ±10V DC of analog common.
(5) Includes offset, gain, nonlinearity, and repeatability error terms.
(6) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(7) Damage may occur to the input circuit if this value is exceeded.
Table 23 - Response Speed - 1769-IF16C
Filter Frequency Step Response Update per Input Pari Update per Module
16 Hz 1550 ms 200 ms 1600 ms
50 Hz 500 ms 70 ms 560 ms
60 Hz 420 ms 60 ms 480 ms
315 Hz 90 ms 15 ms 120 ms
1365 Hz 35 ms 5 ms 40 ms
Table 22 - Technical Specifications - 1769-IF16C
Attribute 1769-IF16C