Technical data
Rockwell Automation Publication 1769-TD006C-EN-P - March 2012 125
1769 Compact I/O Modules Specifications
Maximum Output Current per Point - 24V DC Operation
Maximum Output Current per Module - 24V DC Operation
Temperature Derated Current
0…40 °C (32…104 °F) 1 A
55 °C (131 °F) 0.5 A
60 °C (140 °F) 0.25 A
Temperature Derated Current
0…40 °C (32…104 °F) 4 A
55 °C (131 °F) 2 A
60 °C (140 °F) 1 A
Table 98 - Certifications - 1769-HSC
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-HSC
c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada. See UL File E65584
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E321922
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
0
0.5
1
1.5
30 ˚C (86 ˚F) 40 ˚C (104 ˚F) 50 ˚C (122 ˚F) 60 ˚C (140 ˚F) 70 ˚C (158 ˚F)20 ˚C (68 ˚F)10 ˚C (50 ˚F)0 ˚C (32 ˚F)
Current Derating Based on Temperature
Ambient Temperature
Current per Point (A)
0.25 A at 60 °C (140 °F)
0
1
2
3
4
5
30 ˚C (86 ˚F) 40 ˚C (104 ˚F) 50 ˚C (122 ˚F) 60 ˚C (140 ˚F) 70 ˚C (158 ˚F)20 ˚C (68 ˚F)10 ˚C (50 ˚F)0 ˚C (32 ˚F)
Current Derating Based on Temperature
Ambient Temperature
Current per Module (A)
1 A @ 60°C (140 °F)