Technical data

124 Rockwell Automation Publication 1769-TD006C-EN-P - March 2012
1769 Compact I/O Modules Specifications
Maximum Output Voltage - 24V DC Operation
Maximum Output Current per Point - 5V DC Operation
Maximum Output Current per Module - 5V DC Operation
Temperature Derated Voltage
0…40 °C (32…104 °F) 30V DC
55…60 °C (131…140 °F) 26.4V DC
Temperature Derated Current
0…40 °C (32…104 °F) 1 A
60 °C (140 °F) 0.5 A
Temperature Derated Current
0…40 °C (32…104 °F) 4 A
60 °C (140 °F) 2 A
26
27
28
29
30
31
30 ˚C (86 ˚F) 40 ˚C (104 ˚F) 50 ˚C (122 ˚F) 60 ˚C (140 ˚F) 70 ˚C (158 ˚F)20 ˚C (68 ˚F)10 ˚C (50 ˚F)0 ˚C (32 ˚F)
Voltage Derating Based on Temperature
Volts (DC)
26.4V DC @ 55 °C (131 °F)
Ambient Temperature
0
0.5
1
1.5
30 ˚C (86 ˚F) 40 ˚C (104 ˚F) 50 ˚C (122 ˚F) 60 ˚C (140 ˚F) 70 ˚C (158 ˚F)20 ˚C (68 ˚F)10 ˚C (50 ˚F)0 ˚C (32 ˚F)
Current Derating Based on Temperature
Ambient Temperature
Current per Point (A)
0.5 A @ 60 °C (140 °F)
0
1
2
3
4
5
30 ˚C (86 ˚F) 40 ˚C (104 ˚F) 50 ˚C (122 ˚F) 60 ˚C (140 ˚F) 70 ˚C (158 ˚F)20 ˚C (68 ˚F)10 ˚C (50 ˚F)0 ˚C (32 ˚F)
Current Derating Based on Temperature
Ambient Temperature
Current per Module (A)
2 A @ 60 °C (140 °F)