Specifications
Rockwell Automation Publication 1769-TD006E-EN-P - January 2015 93
1769 Compact I/O Modules Specifications
Accuracy drift with temperature ±0.0058% per °C
Output ripple
(4)
±0.05% @ 0…50 kHz
Nonlinearity ±0.05%
Repeatability
(5)
±0.05%
Module error ±0.55%
Offset error ±0.05%
Output impedance > 1 MΩ
Open and short-circuit protection Yes
Short-circuit protection, max 21 mA
Output overvoltage protection Ye s
Output response at system powerup and power down ±0.5V DC spike for < 5 ms
Rated working voltage
(6)
30V AC/30V DC
Isolation voltage 500V AC or 710V DC for 1 min (qualification test), output group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 281 g (0.62 lb)
Dimensions (HxWxD), approx 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
Module location DIN rail or panel mount
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Optional 24V DC Class 2 power supply voltage range
(7)
20.4…26.4V DC
Power supply distance rating 8 modules
Terminal screw torque 0.68 Nm (6 lbin)
Retaining screw torque 0.46 Nm (4.1 lbin)
Wire size (22…14 AWG) solid
(22…16 AWG) stranded
Wire type Cu-90 °C (194 °F)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Product type code 10
Product code 40
Input words 11
Output words 9
Configuration words 64
Enclosure type rating None (open style)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The
flag automatically resets when within the normal operating range.
(2) Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
Table 82 - Technical Specifications - 1769-OF8C
Attribute 1769-OF8C