Specifications
90 Rockwell Automation Publication 1769-TD006E-EN-P - January 2015
1769 Compact I/O Modules Specifications
Accuracy drift with temperature ±0.0086% FS per °C
Output ripple
(4)
±0.05% @ 0…50 kHz
Nonlinearity ±0.05%
Repeatability
(5)
±0.05%
Module error ±0.8%
Output impedance < 1 Ω
Open and short-circuit protection Yes
Short-circuit protection, max 35 mA typical
42 mA, max
Output overvoltage protection Yes
Output response at system powerup and power down Powerup: ±1.2V DC spike for < 0.4 ms
Power down: ±1.2V DC spike for 21 ms
Rated working voltage
(6)
30V AC/30V DC
Isolation voltage 500V AC or 710V DC for 1 min (qualification test), output group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 270 g (0.60 lbs)
Dimensions (HxWxD), approx 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
Module location DIN rail or panel mount
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Power supply distance rating 8 modules
Terminal screw torque 0.68 Nm (6 lbin)
Retaining screw torque 0.46 Nm (4.1 lbin)
Wire size (22…14 AWG) solid
(22…16 AWG) stranded
Wire type Cu-90 °C (194 °F)
Recommended cable Belden 8761 (shielded)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Product type code 10
Product code 42
Input words 6
Output words 5
Configuration words 32
Enclosure type rating None (open style)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag
automatically resets when within the normal operating range.
(2) Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
Table 79 - Technical Specifications - 1769-OF4VI
Attribute 1769-OF4VI