Specifications
Rockwell Automation Publication 1769-TD006E-EN-P - January 2015 81
1769 Compact I/O Modules Specifications
Load range on voltage output > 1 kΩ @ 10V DC
Inductive load (current outputs), max 0.1 mH
Capacitive load (voltage outputs), max 1 μF
Field calibration None required
Accuracy
(3)
Voltage: ±0.5% full scale @ 25 °C (77 °F)
Current: ±0.35% full scale @ 25 ° C (77 °F)
Accuracy drift with temperature Voltage: ±0.0086% per °C
Current: ±0.0058% per °C
Output ripple
(4)
±0.05% @ 0…50 kHz
Nonlinearity ±0.05%
Repeatability
(5)
±0.05%
Module error Voltage: ±0.8%
Current: ±0.55%
Offset error ±0.05%
Output impedance 15 Ω
Open and short-circuit protection Ye s
Short-circuit protection, max 21 mA
Output overvoltage protection Yes
Time to detect open wire condition (current mode) 10 ms, typical
13.5 ms, max
Output response at system powerup and power down ±5V DC spike for < 5 ms
Rated working voltage
(6)
30V AC/30V DC
Isolation voltage 500V AC or 710V DC for 1 min (qualification test), output group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 300 g (0.65 lb)
Dimensions (HxWxD), approx 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
Module location DIN rail or panel mount
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Optional 24V DC Class 2 power supply voltage range
(7)
20.4…26.4V DC
Power supply distance rating 8 modules
Terminal screw torque 0.68 Nm (6 lbin)
Retaining screw torque 0.46 Nm (4.1 lbin)
Wire size (22…14 AWG) solid
(22…16 AWG) stranded
Wire type Cu-90 °C (194 °F)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Table 73 - Technical Specifications - 1769-OF2
Attribute 1769-OF2