Specifications

Rockwell Automation Publication 1769-TD006E-EN-P - January 2015 49
1769 Compact I/O Modules Specifications
Table 46 - Relay Contact Ratings - 1769-IQ6XOW4
Volts, max Continuous Amps
per Point, max
Amperes
(1)
(1) Connecting surge suppressors across your external inductive load will extend the life of the relay contacts.
Voltamperes NEMA ICS 2-125
Make Break Make Break
240V AC 2.5 A 7.5 A 0.75 A 1800 VA 180 VA C300
120V AC 15 A 1.5 A
125V DC 1.0 A 0.22 A
(2)
(2) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage
applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.
28 VA R150
24V DC 2.0 A 1.2 A
(2)
28 VA
Table 47 - Certifications - 1769-IQ6XOW4
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-IQ6XOW4
c-UL C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
Class I, Division 2 Group A,B,C,D Hazardous Locations (UL 1604, C-UL under CSA C22.2 No. 213)
CE CE compliant for all applicable directives
C-Tick C-Tick compliant for all applicable directives