Specifications
Rockwell Automation Publication 1769-TD006E-EN-P - January 2015 37
1769 Compact I/O Modules Specifications
1769-IM12
Compact 240V AC input module
Table 33 - Technical Specifications - 1769-IM12
Attribute 1769-IM12
Inputs 12 (12 points/group, internally connected commons)
Voltage category 200/240V AC
Operating voltage range 159…265V AC,
47…63 Hz
Input delay, on 20 ms
Input delay, off 20 ms
Current draw @ 5.1V 100 mA
Heat dissipation, max 3.65 W
Off-state voltage, max 40V AC
Off-state current, max 2.5 mA
On-state voltage, min 159V AC
On-state current, min 5 mA @ 74V AC
On-state current, max 12 mA @ 120V AC
Inrush current, max
(1)
250 mA
Input impedance, max 27 kΩ @ 50 Hz
23 kΩ @ 60 Hz
Isolation voltage Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s, input
point to bus
132V AC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 300 g (0.61 lb)
Dimensions (HxWxD), approx 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
IN 7
IN 5
IN 3
IN 1
AC
COM
IN 6
IN 4
IN 2
IN 0
L1
L2
200/240V AC
NC
NC
IN 10
IN 8
AC
COM
NC
NC
IN 11
IN 9
Commons are
connected internally.
1769-IM12
Do not use the NC terminals as a connection.