Specifications

20 Rockwell Automation Publication 1769-TD006E-EN-P - January 2015
1769 Compact I/O Modules Specifications
Output impedance 10 kΩ
Open and short-circuit protection Yes
Short-circuit, max 40 mA
Open circuit, max 15V
Output response at system powerup and power down +2.0…-1.0V DC spike for < 6 ms
Isolation voltage 500V AC or 710V DC for 1 min (qualification test), output group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag
automatically resets when within the normal operating range.
(2) Includes offset, gain, nonlinearity, and repeatability error terms.
(3) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(4) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
Table 15 - Response Speed - 1769-IF4XOF2
Fixed Filter Frequency Filter Cut-off Frequency Step Response %
Complete
Step Response Time
2.7 kHz 2.7 kHz 63 % 59 μs
2.7 kHz 2.7 kHz 90 % 136 μs (nom)
Table 16 - Certifications - 1769-IF4XOF2
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-IF4XOF2
c-UL C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
Class I, Division 2 Group A,B,C,D Hazardous Locations (UL 1604, C-UL under CSA C22.2 No. 213)
CE CE compliant for all applicable directives
C-Tick C-Tick compliant for all applicable directives
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Enclosure
Table 14 - 1769-IF4XOF2 Output Specifications
Attribute 1769-IF4XOF2