Specifications

Rockwell Automation Publication 1769-TD006E-EN-P - January 2015 13
1769 Compact I/O Modules Specifications
Retaining screw torque 0.46 Nm (4.1 lbin)
Wire size (22…14 AWG) solid
(22…16 AWG) stranded
Wire type Cu-90 °C (194 °F)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 series B (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Product type code 10
Product code 35
Enclosure type rating None (open-style)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag
automatically resets when within the normal operating range.
(2) Resolution is dependent upon your filter selection. The maximum resolution is achieved with either the 50 or 60 Hz filter selected.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC
input signal and 20V DC potential above ground).
(4) For proper operation, both the plus and minus input terminals must be within ±10V DC of analog common.
(5) Includes offset, gain, nonlinearity, and repeatability error terms.
(6) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(7) Damage may occur to the input circuit if this value is exceeded.
(8) If the optional 24V DC Class 2 power supply is used, the 24V DC current draw from the bus is 0 mA.
Table 7 - Response Speed - 1769-IF4
Filter Frequency Cut-off Frequency Step Response Channel Update
50 Hz 13.1 Hz 60 ms 22 ms
60 Hz 15.7 Hz 50 ms 19 ms
250 Hz 65.5 Hz 12 ms 6 ms
500 Hz 131 Hz 6 ms 4 ms
Table 8 - Certifications - 1769-IF4
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-IF4
c-UL C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
Class I, Division 2 Group A,B,C,D Hazardous Locations (UL 1604, C-UL under CSA C22.2 No. 213)
CE CE compliant for all applicable directives
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Enclosure
Table 6 - Technical Specifications - 1769-IF4
Attribute 1769-IF4