Specifications

43
1768-SG001A-EN-P -- March 2006
CompactLogix Selection Guide
Step 6 - Select:
y
Panel mount or DIN rail mount
y
Appropriate number of panels or DIN
rails based on the number of modules
and the physical location
y
Expansion cables
Mount the CompactLogix System
You can panel mount or DIN-rail mount a CompactLogix system. The CompactLogix system
must be mounted so that the modules are horizontal to each other.
If you decide to use a DIN rail, use steel, 35 x 7.55mm DIN rails (A-B part number 199-
DR1; 46277-3; EN 50022). The DIN rails for all CompactLogix system components must be
mounted on a common, conductive surface to be sure of proper electromagnetic
interference (EMI) performance.
SSeelleecctt EExxppaannssiioonn CCaabblleess
y
One end cap per controller system
How you orient I/O banks determines which expansion cables you need to connect the
I/O banks.
IIff YYoouu AAdddd aa:: AAnndd CCoonnnneecctt tthhee CChhaassssiiss:: UUssee TThhiiss CCaabbllee::
Second bank
right to left 1769-CRLx
right to right 1769-CRRx
Third bank
right to left 1769-CRLx
right to right 1769CRRx
left to left 1769-CLLx
Where x = 1 for 1 ft (305 mm) or 3 for 3.28 ft (1 m).
FFoorr aa OOrrddeerr
Right end cap 1769-ECR
Left end cap 1769-ECL
SSeelleecctt EEnndd CCaappss
The final I/O bank in the CompactLogix system needs an end cap on the end without the
expansion cable.