Technical data

8 Rockwell Automation Publication 1769-TD005I-EN-P - August 2014
CompactLogix Controllers Specifications
I/O Module Support - CompactLogix 5370 L1 Controllers
The CompactLogix 5370 L1 controllers offer an embedded I/O module and the option of using 1734 POINT I/O
modules as local expansion modules.
The embedded I/O module provides the following:
16 sinking 24V DC digital input points
16 sourcing 24V DC digital output points
To use 1734 POINT I/O modules as local expansion modules, keep in mind the following:
Local expansion modules must be installed in the same system as the CompactLogix 5370 L1 controller.
The modules are installed to the right of the controller.
The maximum number of local expansion modules available depends on the controller catalog of that system.
Table 4
lists the number of 1734 POINT I/O modules the CompactLogix 5370 L1 controllers support. Each I/O
module’s minimum RPI is 1.0 ms and can be changed by 0.5 ms increments.
Table 4 - 1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B Controllers - Local I/O Module Support
Cat. No. Local 1734 POINT I/O Modules Supported, max
1769-L16ER-BB1B 6
1769-L18ER-BB1B 8
1769-L18ERM-BB1B
Local Expansion ModulesEmbedded I/O Module