Technical data
Rockwell Automation Publication 1769-TD005I-EN-P - August 2014 47
CompactLogix Controllers Specifications
Real-time Clock Accuracy
The following table lists the real-time clock accuracy specifications for the 1769 Modular CompactLogix controllers.
Panel-mounting screw torque 1.1…1.8 Nm (10…16 lbin) - use M4 or #8 screws
Power supply distance rating 4 modules
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Wire category
(1)
2 - on communication ports
North American temperature code T5 T4A
IEC temperature code NA NA T4 NA T4
Enclosure type rating None (open-style)
(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 33 - Certifications - 1769 Modular CompactLogix Controllers
Certification
(1)
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1769-L31 1769-L32C, 1769-L35CR 1769-L32E, 1769-L35E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EX —
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection ’n’
• EN 60079-0; General Requirements (Zone 2)
• II 3 G Ex nA IIC T4 Gc
CI — ControlNet International conformance tested to
ControlNet specifications
—
EtherNet/IP — — ODVA conformance tested to EtherNet/IP specifications.
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
Ambient Temperature Accuracy
0 °C (32 °F) 54…-56 s/mo
25 °C (77 °F) 9…-124 s/mo
40 °C (104 °F) -84…-234 s/mo
55 °C (131 °F) -228…-394 s/mo
60 °C (140 °F) -287…-459 s/mo
Table 32 - Technical Specifications - 1769 Modular CompactLogix Controllers
Attribute 1769-L31 1769-L32C 1769-L32E 1769-L35CR 1769-L35E