Technical data

Rockwell Automation Publication 1769-TD005I-EN-P - August 2014 3
CompactLogix Controllers Specifications
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 1890 MHz
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
1769-L31,
1769-L32C,
1769-L35CR
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 1890 MHz
1769-L32E,
1769-L35E
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 1890 MHz
3V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
@ 1890 MHz
3V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
EFT/B immunity
IEC 61000-4-4
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
±3 kV at 5 kHz on communication ports
±3 kV at 5 kHz on
communication
ports
±2 kV at 5 kHz on
power ports
±2 kV at 5 kHz on
signal ports
±2 kV at 5 kHz on
communication
ports
1769-L31,
1769-L32C,
1769-L35CR
±2 kV at 5 kHz on
communication
ports
1769-L32E,
1769-L35E
±3 kV at 5 kHz on
power ports
±3 kV at 5 kHz on
communication
ports
±4 kV at 5 kHz on
communication
ports
Surge transient immunity
IEC 61000-4-5
+ 1 kV line-line (DM)
and +
2 kV line-
earth (CM) on power
ports
+
1 kV line-line (DM)
and +
2 kV line-
earth (CM) on signal
ports
+
2 kV line-earth
(CM) on
communication
ports
±1 kV line-line (DM)
and +
2 kV line-earth
(CM) on power ports
±1 kV line-line (DM)
and +
2 kV line-earth
(CM) on signal ports
+
2 kV line-earth
(CM) on shielded
ports
±2 kV line-earth
(CM) on
communication
ports
±2 kV line-earth
(CM) on
communication
ports
±1 kV line-line (DM)
and +
2 kV line-earth
(CM) on power ports
±1 kV line-line (DM)
and +
2 kV line-earth
(CM) on signal ports
+
2 kV line-earth
(CM) on shielded
ports
±2 kV line-earth
(CM) on
communication
ports
1769-L31
Channel 0: ±2 kV
line-earth (CM) on
shielded ports
Channel 1: ±1 kV
line-earth (CM) on
shielded ports
1769-L32C,
1769-L35CR,
1769-L32E,
1769-L35E
±2 kV line-earth
(CM) on
communication
ports
±2 kV line-earth
(CM) on
communication
ports
Conducted RF immunity
IEC 61000-4-6
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
(1) If you are mounting a CompactLogix™ 5370 L1 controller on a EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, you must first adhere a bumper on the back of the controller. Failure to install the bumper
before mounting the controller results in the system failing to meet this specification. For more information, see the CompactLogix 5370 Controllers User Manual, publication 1769-UM021
.
(2) If you are mounting a CompactLogix 5370 L1 controller on a EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, the Shock, nonoperating specification = 30 g.
Table 1 - Environmental Specifications - 1768 and 1769 CompactLogix Controllers and CompactLogix 5370 Controllers
Attribute 1769-L16ER-BB1B,
1769-L18ER-BB1B,
1769-L18ERM-
BB1B
1769-L24ER-QB1B,
1769-L24ER-
QBFC1B, 1769-
L27ERM-QBFC1B
1769-L30ER,
1769-L30ER-NSE,
1769-L30ERM,
1769-L33ER,
1769-L33ERM,
1769-L36ERM
1769-L23-QBFC1B,
1769-L23E-QB1B,
1769-L23E-
QBFC1B
1769-L31,
1769-L32C,
1769-L35CR,
1769-L32E,
1769-L35E
1768-L43,
1768-L43S,
1768-L45,
1768-L45S