Technical data

Rockwell Automation Publication 1769-TD005I-EN-P - August 2014 27
CompactLogix Controllers Specifications
I/O Module Support - CompactLogix 5370 L3 Controllers
The CompactLogix 5370 L3 controllers offer local expansion modules that are installed across up to three banks of
modules. You must use 1769 Compact I/O modules with these controllers.
Remember the following when using I/O modules with the CompactLogix 5370 L3 controllers:
The controller must be the leftmost module in the local bank of the system.
The number of I/O modules that are supported in a controller system varies by controller catalog number.
You can install I/O modules in as many as three banks, that is, the local bank and two additional banks.
You can install as many as three I/O modules between the controller and power supply.
You can install as many as eight I/O modules to the right of the power supply in the local bank or on both the left
and right sides of the power supply in additional banks.
You must consider the controller’s and all I/O modules’ distance rating and current draw when designing you system.
Systems with multiple banks can be installed vertically or horizontally.
You must use expansion cables to connect banks in multi-bank systems.
You must terminate the end of the last bank in a system.
Cat. No. Local 1769 Compact I/O Modules Supported, max
1769- L30ER
1769-L30ERM
1769-L30ER-NSE
8
1769-L33ER
1769-L33ERM
16
1769-L36ERM 30
Horizontal Orientation
Vertical Orientation
Local Bank Additional Bank
Additional Bank
Additional Bank
Local Bank
1769-CRL1 Compact I/O Communication
Bus Expansion Cables
1769-CRR1 Compact I/O Communication
Bus Expansion Cables
End Cap
End Cap