Technical data
2 Rockwell Automation Publication 1769-TD005I-EN-P - August 2014
CompactLogix Controllers Specifications
Table 1 - Environmental Specifications - 1768 and 1769 CompactLogix Controllers and CompactLogix 5370 Controllers
Attribute 1769-L16ER-BB1B,
1769-L18ER-BB1B,
1769-L18ERM-
BB1B
1769-L24ER-QB1B,
1769-L24ER-
QBFC1B, 1769-
L27ERM-QBFC1B
1769-L30ER,
1769-L30ER-NSE,
1769-L30ERM,
1769-L33ER,
1769-L33ERM,
1769-L36ERM
1769-L23-QBFC1B,
1769-L23E-QB1B,
1769-L23E-
QBFC1B
1769-L31,
1769-L32C,
1769-L35CR,
1769-L32E,
1769-L35E
1768-L43,
1768-L43S,
1768-L45,
1768-L45S
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
-20…60 °C
(-4…140 °F)
0…60 °C
(32…140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
-40…85 °C
(-40…185 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
(1)
5 g @ 10…500 Hz 2 g @ 10…500 Hz 5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
(1)
20 g - DIN rail
30 g - Panel
30 g 20 g - DIN rail
30 g - Panel
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
(1)
,
(2)
30 g - DIN rail
40 g - Panel
50 g 30 g - DIN rail
40 g - Panel
50 g
Emissions
CISPR 11
Class A
(IEC 61000-6-4)
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
4 kV contact
discharges
8 kV air discharges
1769-L31
4 kV contact
discharges
8 kV air discharges
1769-L32C, 1769-
L35CR, 1769-L32E,
1769-L35E
6 kV contact
discharges
8 kV air discharges
6 kV contact
discharges
8 kV air discharges