Installation Instructions Compact™ AC/DC Relay Output Module (Catalog Number 1769-OW8, Series B) Inside Module Description ................................................................................. 2 Module Installation.................................................................................. 3 System Assembly..................................................................................... 4 Mounting Expansion I/O ........................................................................
Compact™ AC/DC Relay Output Module Module Description 1 Item Description 2a 3 1 bus lever (with locking function) 2a upper panel mounting tab 2b lower panel mounting tab 3 I/O diagnostic LEDs 4 module door with terminal identification label 5a movable bus connector with female pins 5b stationary bus connector with male pins 6 nameplate label 7a upper tongue-and-groove slots 7b lower tongue-and-groove slots 8a upper DIN rail latch 8b lower DIN rail latch 9 write-on label (us
Compact™ AC/DC Relay Output Module 3 Module Installation Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2(1)) and to circuits not exceeding Over Voltage Category II(2) (IEC 60664-1).(3) Prevent Electrostatic Discharge ATTENTION ! Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins.
Compact™ AC/DC Relay Output Module System Assembly The module can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see "Panel Mounting" on page 5, or "DIN Rail Mounting" on page 7. To work with a system that is already mounted, see "Replacing a Single Module within a System" on page 7. The following procedure shows you how to assemble the Compact I/O system. 3 4 2 1 6 1 5 1. Disconnect power. 2.
Compact™ AC/DC Relay Output Module 5 7. Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before. 8. Lock the end cap bus terminator (6). IMPORTANT A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus. Mounting Expansion I/O ATTENTION ! During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module.
Compact™ AC/DC Relay Output Module Panel Mounting Using the Dimensional Template Compact I/O End Cap 28.5 (1.12) 35 (1.38) Compact I/O 122.6±0.2 (4.826±0.008) Compact I/O 132 (5.197) Host Controller For more than 2 modules: (number of modules - 1) x 35 mm (1.38 in.) Refer to host controller documentation for this dimension. Note: All dimensions are in mm (inches). Hole spacing tolerance: ±0.4 mm (0.016 in.).
Compact™ AC/DC Relay Output Module 7 DIN Rail Mounting The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15). Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place. Replacing a Single Module within a System The module can be replaced while the system is mounted to a panel (or DIN rail). 1.
Compact™ AC/DC Relay Output Module Field Wiring Connections Grounding the Module This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
Compact™ AC/DC Relay Output Module 9 A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed. SLOT # _____ MODULE TYPE ______ Removing the Finger-Safe Terminal Block When wiring field devices to the module, it is not necessary to remove the terminal block.
Compact™ AC/DC Relay Output Module 2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug. TIP The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch minimum i.d. (M3.5)] with the module. 3. Tighten the terminal screw making sure the pressure plate secures the wire. Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
Compact™ AC/DC Relay Output Module 11 I/O Memory Mapping Output Data File For each module, slot x, word 0 in the output data file contains the control program’s directed state of the discrete output points. For the 1769-OW8, bits 8 to 15 are not used.
Compact™ AC/DC Relay Output Module 1769-OW8 Configuration File The read/writable configuration data file allows the setup of the hold last state and user-defined safe state conditions. Word The manipulation of the bits from this file is normally done with programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided via the programmer to simplify configuration. However, some systems (e.g.
Compact™ AC/DC Relay Output Module 13 Fault Value Word The fault value word, word 4, is used to program the fault state value (0=Off, 1=On). Each output is individually configurable for on or off.
Compact™ AC/DC Relay Output Module Specifications General Specifications Specification Value Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm 4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in. Approximate Shipping Weight (with carton) 280g (0.61 lbs.
Compact™ AC/DC Relay Output Module 15 Output Specifications Specification 1769-OW8 Voltage Category AC/DC normally open relay Operating Voltage Range 5 to 265V ac 5 to 125V dc Number of Outputs 8 Bus Current Draw (max.) 125 mA at 5V dc (0.625W) 100 mA at 24V dc (2.4W) Heat Dissipation 2.83 Total Watts (The Watts per point, plus the minimum Watts, with all points energized.) Signal Delay (max.) – resistive load turn-on = 10 ms turn-off = 10 ms Off-State Leakage (max.
Compact™ AC/DC Relay Output Module Relay Contact Ratings Volts (max.) 240V ac Continuous Amps per Point (max.) 2.5A 120V ac Amperes(1) Voltamperes Make Break Make Break 7.5A 0.75A 1800 VA 180 VA 15A 1.5A NEMA ICS 2-125 C300 125V dc 1.0A 0.22A(2) 28 VA R150 24V dc 2.0A 1.2A(2) 28 VA — (1) (2) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay contacts.
Compact™ AC/DC Relay Output Module 17 Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. WARNING ! EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Compact™ AC/DC Relay Output Module For More Information For Refer to this Document Pub. No. A more detailed description of how to install MicroLogix 1200 & 1500 and use your Compact™ I/O with MicroLogix™ Programmable Controllers User 1200 & 1500 programmable controller. Manual 1764-UM001B-US-P A more detailed description of how to install 1769-ADN DeviceNet Adapter User and use your Compact I/O with the 1769-ADN Manual DeviceNet Adapter.
Compact™ AC/DC Relay Output Module 19 Publication 1769-IN051A-EN-P - April 2001
Compact, MicroLogix, CompactLogix, RSLogix and RSNetworx are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). Publication 1769-IN051A-EN-P - April 2001 Supersedes Publication 1769-IN003C-EN-P - June 2000 PN 40072-115-01 (A) © 2001 Rockwell International Corporation. Printed in the U.S.A.