Installation Instructions Compact™ 16-Point AC/DC Relay Output Module (Catalog Number 1769-OW16) Inside Module Description ................................................................................. 2 Module Installation.................................................................................. 3 System Assembly..................................................................................... 4 Mounting Expansion I/O ........................................................................
Compact™ 16-Point AC/DC Relay Output Module Module Description The 1769-OW16 is a 16 point relay output module that can control AC or DC loads. The module has 2 isolated groups of 8 points each. This allows you to mix both AC and DC loads on one module.
Compact™ 16-Point AC/DC Relay Output Module 3 Module Installation Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2(1)) and to circuits not exceeding Over Voltage Category II(2) (IEC 60664-1).(3) Prevent Electrostatic Discharge ATTENTION ! Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins.
Compact™ 16-Point AC/DC Relay Output Module System Assembly The module can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see "Panel Mounting" on page 5, or "DIN Rail Mounting" on page 7. To work with a system that is already mounted, see "Replacing a Single Module within a System" on page 7. The following procedure shows you how to assemble the Compact I/O system. 3 4 2 1 6 1 5 1. Disconnect power. 2.
Compact™ 16-Point AC/DC Relay Output Module 5 7. Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before. 8. Lock the end cap bus terminator (6). IMPORTANT A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus. Mounting Expansion I/O ATTENTION ! During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module.
Compact™ 16-Point AC/DC Relay Output Module Panel Mounting Using the Dimensional Template Host Controller Spacing for single-wide modules 35 mm (1.378 in.) Spacing for one-and-a half-wide modules 52.5 mm (2.067 in.) Refer to host controller documentation for this dimension. Note: Overall hole spacing tolerance: ±0.4 mm (0.016 in.). Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and one-and-a-half-wide modules (e.g. 1769-OA16).
Compact™ 16-Point AC/DC Relay Output Module 7 DIN Rail Mounting The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15). Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place. Replacing a Single Module within a System The module can be replaced while the system is mounted to a panel (or DIN rail).
Compact™ 16-Point AC/DC Relay Output Module Field Wiring Connections Grounding the Module This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
Compact™ 16-Point AC/DC Relay Output Module 9 A removable, write-on label, (see page 2, item 9) is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed. Removing the Finger-Safe Terminal Block When wiring field devices to the module, it is not necessary to remove the terminal block.
Compact™ 16-Point AC/DC Relay Output Module 2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug. TIP The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch minimum i.d. (M3.5)] with the module. 3. Tighten the terminal screw making sure the pressure plate secures the wire. Recommended torque when tightening terminal screws is 0.
Compact™ 16-Point AC/DC Relay Output Module 11 I/O Memory Mapping Output Data File Data output bits are turned on or off using the bit positions in Word 0. 1 = output on 0 = output off Example: To turn on bit position 12, type 1 in Word 0, Bit 12. For each module, slot x, word 0 in the output data file contains the control program’s directed state of the discrete output points.
Compact™ 16-Point AC/DC Relay Output Module 1769-OW16 Configuration File The read/writable configuration data file allows the setup of the hold last state and user-defined safe state conditions. Word The manipulation of the bits from this file is normally done with programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided via the programmer to simplify configuration. However, some systems (e.g.
Compact™ 16-Point AC/DC Relay Output Module 13 Fault Value Word The fault value word, word 4, is used to program the fault state value (0=Off, 1=On). Each output is individually configurable for on or off.
Compact™ 16-Point AC/DC Relay Output Module Specifications General Specifications Specification Value Dimensions 118 mm (height) x 87 mm (depth) x 52.5 mm (width) height including mounting tabs is 138 mm 4.65 in. (height) x 3.43 in (depth) x 2.07 in (width) height including mounting tabs is 5.43 in. Approximate Shipping Weight (with carton) 450g (0.99 lbs.
Compact™ 16-Point AC/DC Relay Output Module 15 Output Specifications Specification 1769-OW16 Voltage Category AC/DC normally open relay Operating Voltage Range 5 to 265V ac 5 to 125V dc Number of Outputs 16 Bus Current Draw (max.) 205 mA at 5V dc line 180 mA at 24V dc line Heat Dissipation 4.75 Total Watts (The Watts per point, plus the minimum Watts, with all points energized.) Signal Delay (max.) – resistive load turn-on = 10 ms turn-off = 10 ms Off-State Leakage (max.
Compact™ 16-Point AC/DC Relay Output Module Relay Contact Ratings Volts (max.) 240V ac Continuous Amps per Point (max.)(1) 2.5A 120V ac Amperes(2) Voltamperes Make Break Make Break 7.5A 0.75A 1800 VA 180 VA 15A 1.5A 125V dc 1.0A 0.22A(3) 24V dc 2.0A 1.2A(3) (1) (2) (3) 28 VA NEMA ICS 2-125 C300 R150 The continuous current per module must be limited so the module power does not exceed 1440 VA.
Compact™ 16-Point AC/DC Relay Output Module 17 Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. WARNING ! EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Compact™ 16-Point AC/DC Relay Output Module For More Information For Refer to this Document Pub. No. A more detailed description of how to install MicroLogix 1500 Programmable and use your Compact™ I/O with MicroLogix™ Controllers User Manual 1200 & 1500 programmable controller. 1764-UM001B-US-P A more detailed description of how to install and use your Compact I/O with the CompactLogix™ System.