Manual

Publication 1769-UM014B-EN-P - May 2010
Module Data, Status, and Channel Configuration for the Output Modules 4-9
1769-OF4CI and -OF4VI Enable/Disable Channel
This configuration selection (bit 15 of Configuration Word 0) allows each
channel to be individually enabled.
Table 4.7 1769-OF4CI and -OF4VI Output Channel Configuration Word 1
Define Indicate Bit Settings
1514131211109876543210
1769-OF4CI
Output
Range
Select
0…20 mA dc
000
4…20 mA dc
001
Output
Data
Select
Raw/Proportion
al Counts
0 0 0
Engineering
Units
001
Scaled for PID 010
Percent Range 0 1 1
1769-OF4VI
Output
Range
Select
-10…+10V dc
000
0…5V dc
001
0…10V dc
010
1…5V dc
011
Output
Data
Select
Raw/Proportion
al Counts
000
Engineering
Units
001
Scaled for PID 010
Percent Range 011
TIP
A channel that is not enabled has zero voltage or current at
its terminal.