User Manual

18 Compact 32-point Solid-state 24V dc Source Output Module
Publication 1769-IN080A-EN-P - August 2006
Program State Word
Word 1, the program state word, selects the hold
last state or user-defined safe state condition for
each individual output on a system transition
from Run to Program.
Program Value Word
The program value word, word 2, is used to
program the user-defined safe state value (0=Off,
1=On). Each output is individually configurable
for on or off.
Fault State Word
Word 3, the fault state word, selects the hold last
state or user-defined safe state condition for each
individual output on a system transition from Run
to Fault.
Fault Value Word
The fault value word, word 4, is used to program
the fault state value (0=Off, 1=On). Each output
is individually configurable for on or off.
9 Fault Value for Output Array Word 1
10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
13 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
14 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Configuration File
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Condition Bit Setting
User-defined safe state 0
Hold last state 1
Value Bit Setting
Off 0
On 1
Condition Bit Setting
User-defined safe state 0
Hold last state 1
Value Bit Setting
Off 0
On 1