Installation Instructions Instruction Manual
1769-L32C, 1769-L35CR CompactLogix Controller 19
Publication
1769-IN070C-EN-P - May 2008
Mount the System
Maintain spacing from items such as enclosure walls, wireways, and adjacent
equipment. Allow 50 mm (2 in.) of space on all sides, as shown. This provides
ventilation and electrical isolation.
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris (such
as metal chips or wire strands) is kept from falling into the controller. Debris
that falls into the controller could cause damage while the controller is
energized.
ATTENTION
When attaching the controller, power supply, and I/O modules, make sure the
bus connectors are securely locked together to be sure of proper electrical
connection.
IMPORTANT
When mounting the CompactLogix system, either use screws to panel
mount system or use DIN rail. Do not use both. Use of both mounting
methods may cause hardware damage and cause the system to fail.
50 mm
(2 in.)
CompactLogix Controller
Compact I/O Module
Power Supply
Compact I/O Module
End Cap
50 mm
(2 in.)
50 mm
(2 in.)
50 mm
(2 in.)