Quick Start CompactLogix 5370 L3 Controllers Catalog Numbers 1769-L30ER, 1769-L30ERM, 1769-L30ER-NSE, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
Where to Start Follow the path that matches your hardware and network configuration. Prepare the CompactLogix 5370 L3 Controller Hardware Required page 17 Required Prepare the Computer and Load Controller Firmware page 33 Optional POINT I/O™ Modules PowerFlex® 40 Drive PowerFlex 70 Drive Kinetix® 350 Drive PanelView™ Plus Terminal PORT MOD NET B NET A STS For more information on using each optional device, see Table 1 on page 12.
Where to Start How Hardware Is Connected This quick start, in use with the additional quick starts listed in Table 1 on page 12, describes possible control systems shown in Figure 1 and Figure 2.
Where to Start Figure 2 - CompactLogix 5370 L3 Controllers Using a DeviceNet Network Distributed POINT I/O Modules with 1734-ADN Adapter CompactLogix 5370 L3 Control System with 1769-SDN Module PowerFlex 70 Drive with 20-COMM-D Adapter 1 (Front) 2 (Rear) Computer with 1784-U2DN Cable 1606-XLDNET4 DeviceNet Power Supply PowerFlex 40 Drive with 22COMM-D Adapter Application Configuration RSNetWorx™ for DeviceNet Software Configuration Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012
Where to Start Sample Panel Layout The sample panel layout shows the orientation of an example CompactLogix 5370 L3 control system using EtherNet/IP networks and DeviceNet networks. IMPORTANT The specific layout of CompactLogix 5370 L3 control systems varies by application. The following graphic is an example panel layout. The graphic shows a PowerFlex 40 drive used on a DeviceNet network. You can also use a PowerFlex 40 drive on an EtherNet/IP network.
Table of Contents Preface About the CompactLogix L3 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . Choose to Integrate Optional Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Chapter 4 Configure the DeviceNet Network Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . What You Need. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apply Power to the DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface This quick start describes how to use CompactLogix 5370 L3 controllers to install a simple CompactLogix 5370 L3 control system and execute a task with a local 1769 Compact I/O output module. The programming examples included are not complex, and offer solutions to verify that devices are functioning and communicating properly. IMPORTANT Consider the following points: • A typical CompactLogix 5370 L3 control system includes more components than listed in this quick start.
Preface About the CompactLogix L3 Controllers These CompactLogix 5370 L3 controllers are available: • 1769-L30ER • 1769-L30ERM • 1769-L30ER-NSE • 1769-L33ER • 1769-L33ERM • 1769-L36ERM IMPORTANT The tasks described in this publication use a 1769-L36ERM controller. These features are available on CompactLogix 5370 L3 controllers.
Preface • I/O module options: – 1769 Compact I/O modules as local expansion module – Control of distributed I/O modules over a DeviceNet or EtherNet/IP network • Support for Integrated Motion on the EtherNet/IP network with the 1769-L30ERM, 1769-L33ERM, 1769-L36ERM controllers only.
Preface Choose to Integrate Optional Devices You can integrate multiple optional devices into a CompactLogix 5370 L3 control system. You can use these devices on DeviceNet or EtherNet/IP networks. This table describes optional devices you might use in a CompactLogix 5370 L3 control controller system and what resources to use for each.
Preface Studio 5000 Environment The Studio 5000™ Engineering and Design Environment combines engineering and design elements into a common environment. The first element in the Studio 5000 environment is the Logix Designer application. The Logix Designer application is the rebranding of RSLogix™ 5000 software and will continue to be the product to program Logix5000™ controllers for discrete, process, batch, motion, safety, and drive-based solutions.
Preface Required Software Before attempting to complete any of the tasks described in this publication, verify that your computer meets the following operating system and service pack compatibility requirements: • Microsoft Windows 7 Professional (64-bit) with Service Pack 1 • Microsoft Windows 7 Home Premium (64-bit) with Service Pack 1 • Microsoft Windows 7 Home Premium (32-bit) with Service Pack 1 • Microsoft Windows Server 2008 R2 Standard Edition with Service Pack 1 If your computer does not meet the
Preface Parts List Table 3 lists the hardware used in this quick start. For example, if you do not intend to use a DeviceNet network to complete tasks described in some publications listed in Table 1, you do not need the hardware related to installing a DeviceNet network. Specific hardware requirements are listed at the beginning of each chapter. Table 3 - Parts Used with This Quick Start Quantity Cat. No.
Preface Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description CompactLogix 5370 Controllers User Manual, publication 1769-UM021 Describes how to design, install, operate, and troubleshoot a CompactLogix 5370 control system.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware This chapter describes how to install the hardware needed for your CompactLogix 5370 L3 control system. Before You Begin Determine which network or networks your control system uses. You can use CompactLogix 5370 L3 controllers on an EtherNet/IP network and on a DeviceNet network.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware What You Need Table 4 lists the hardware components used in this chapter. The parts listed in this table are done so with the assumption that you will install an EtherNet/IP and DeviceNet network. Table 4 - Parts Used with This Quick Start Quantity Cat. No.
Prepare the CompactLogix 5370 L3 Controller Hardware Follow These Steps Install the Networks page 20 Install the Secure Digital Card page 21 Assemble the System page 23 Make Network Connections page 26 Wire Power page 32 Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012 Chapter 1 1 (Front) 2 (Rear) 19
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware Install the Networks Before you install your CompactLogix 5370 L3 control hardware, you must install the network on which it will operate, that is, an EtherNet/IP or DeviceNet network. We recommend that you install both networks. For more information on installing either of these networks, see the publications listed in the following table.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 Install the Secure Digital Card The secure digital (SD) card provides nonvolatile storage for the CompactLogix 5370 L3 controller. You can store projects to an SD card or load a project from an SD card. There following SD cards are available with for use with your CompactLogix 5370 L3 controller.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware 3. Insert the SD card into the SD card slot. You can install the SD card in one orientation only. The beveled corner should be at the top. An orientation logo is printed on the card. If you feel resistance when inserting the SD card, pull it out and change the orientation. 4. Gently press the card until it clicks into place. 5. Close the SD card door.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 Assemble the System CompactLogix 5370 L3 control systems support multiple system configurations, including the optional placement of modules between the controller and the power supply and to the right of the power supply. Complete the following steps to assemble the system. 1. Make sure that line power is disconnected. 2. Make sure that the lever of the 1769 Compact power supply is in the unlocked position, that is, leaning to the right.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware 5. Move the power supply’s bus level fully to the left until it locks. 6. Mount the CompactLogix 5370 L3 controller and power supply on the DIN rail. a. Pull locking tabs out b. Slide controller and power supply into position. c. Push the locking tabs in. 7. Mount the 1769-OB16 output module. a. Make sure the output module’s locking tabs are pulled out and the module’s bus lever is in the unlocked position, that is, leaning to the right.. b.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 8. Install the 1769-SDN scanner module. a. Make sure the scanner module’s locking tabs are pulled out. b. Make sure the scanner module’s bus lever is in the unlocked position, that is, leaning to the right. c. Use the upper and lower tongueand-groove slots to secure the scanner module and power supply together. d. Move the scanner module back along the tongue-and-groove slots until the bus connectors line up with each other. e.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware 9. Mount the 1769-ECR end cap terminator. a. Move the end cap terminator’s bus lever to the unlocked position, that is, the right. b. Move the end cap terminator back along the tongue-andgroove slots with the rightmost module in the system until the bus connectors line up with each other. c. Move the end cap terminator’s bus lever fully to the left until it locks.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 Make USB Connection IMPORTANT You must use RSLinx Classic software, version 2.59.xx or later, with your CompactLogix 5370 L3 controllers. With this software version, there is no need to install an RSLinx Classic software driver. The driver appears automatically in the software when a USB cable is connected to the controller and the computer. The controller has a USB port that uses a Type B receptacle. The port is USB 2.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware Make an EtherNet/IP Network Connection IMPORTANT This section assumes that you installed a 1783-EMS08T Stratix 6000 Ethernet managed switch on the DIN rail when you installed your EtherNet/IP network as described on Install the Networks on page 20. 1. Plug a 1585J-M4TBJM-1, Ethernet cable (straight-through) into a port on the Stratix 6000. 2.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 Make a DeviceNet Network Connection (Optional) 1. Attach and lock the 1606-XLDNET8 DeviceNet power supply to the DIN rail. 1606-X POWE AC 120 The power supply uses a locking tab at the top that you push down to secure it to the DIN rail. 2. Assemble the DeviceNet network cable system using the KwikLink flat cable, terminators, and sealed micro connectors for each device. See instructions included with devices.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware 4. Connect the 1769-SDN module’s grounding screw to the panel. Grounding Screw Use 2.08 mm2 (14 AWG) wire to connect to panel ground. 5. Connect the QD Micro Cordset to a KwikLink sealed microconnector on the network. 6. Wire the 1606-XLDNET8 DeviceNet power supply. WARNING: Verify that all incoming power is turned off before wiring power. a. Connect incoming power to the power supply.
Prepare the CompactLogix 5370 L3 Controller Hardware Chapter 1 c. Connect the DeviceNet power tap to the power supply. Connect To Red + White N/A Shield N/A Blue N/A Black – For this example, there is no need to connect the DC ok relay on the power supply to anything. ATTENTION: If you have unused DeviceNet wires, make sure they do not come into contact with the other wires. 7. Connect the DeviceNet power tap to the DeviceNet network. 8. Do not turn on incoming power.
Chapter 1 Prepare the CompactLogix 5370 L3 Controller Hardware Wire Power 1769-PA4 Power Supply WARNING: Verify that all incoming power is turned off before wiring power. 1. Set the V AC line input power switch behind the clear door to match your 120V or 240V AC power source as directed by the DANGER label on the power supply. The switch is shipped from the factory in the 240V AC position. Remove the switch label that covers the connectors after setting the proper power switch. 2.
Chapter 2 Prepare the Computer and Load Controller Firmware In this chapter, you install and configure the necessary programming and configuration software on your computer and load firmware on your controller. Before You Begin Before you begin, complete these tasks: • Verify that your computer meets the software’s system requirements for installation and use of the software listed in Table 5.
Chapter 2 Prepare the Computer and Load Controller Firmware What You Need Table 5 lists the components you use in this chapter. Table 5 - What You Need to Prepare the Computer Component Description Studio 5000 environment Environment that combines engineering and design elements into a common environment. Logix Designer application Application used to create a project the CompactLogix 5370 L3 controller uses in your application.
Prepare the Computer and Load Controller Firmware Chapter 2 Follow These Steps Install the Studio 5000 Environment page 36 Configure an EtherNet/IP Driver in RSLinx Classic Software page 38 Set the IP Address for the Computer page 41 Load the Controller Firmware page 44 Optional Install Additional Software page 48 Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012 35
Chapter 2 Prepare the Computer and Load Controller Firmware Install the Studio 5000 Environment The Studio 5000 environment, version 21.00.00, installation process is configured so that, among other software applications, RSLinx Classic software, version 3.51.00 and RSNetWorx for DeviceNet software, version 21.00.00, are automatically installed. The automatic installation option is enabled by default.
Prepare the Computer and Load Controller Firmware Chapter 2 3. Use the default selections and click Install. 4. Read the license agreement carefully. 5. Click Accept All. The installation process begins. When installation is complete, your computer will have the software necessary required to complete the tasks described in this publication. Among other software, your computer will have the following: • Studio 5000 Environment, version 21.00.00 • • The Studio 5000 Environment, version 21.00.
Chapter 2 • Prepare the Computer and Load Controller Firmware Rockwell Automation Technical Support Software Activations site http:// www.rockwellautomation.com/support/activations.html Automatic Installation of ControlFLASH Software ControlFLASH software is used to upgrade a CompactLogix 5370 L3 controller’s firmware revision. ControlFLASH software is automatically installed when you install the Studio 5000 environment.
Prepare the Computer and Load Controller Firmware Chapter 2 2. From the Communications pulldown menu, choose Configure Drivers. The Configure Drivers dialog box appears. 3. From the Available Driver Types pull-down menu, choose EtherNet/IP Driver or Ethernet devices and click Add New. We recommend that you use EtherNet/IP Driver. The Add New RSLinx Driver dialog box appears. 4. Click OK to keep the default name. A Configure driver:AB_ETHxxx dialog box appears.
Chapter 2 Prepare the Computer and Load Controller Firmware 5. Select an Ethernet card and click OK. This new driver is available. 6. Verify that the driver’s Status is Running and click Close.
Prepare the Computer and Load Controller Firmware Chapter 2 Set the IP Address for the Computer Your computer requires an Internet Protocol (IP) address to operate on an EtherNet/IP network. The IP address uniquely identifies the controller and is in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254 with some exceptions for reserved values. A computer’s IP address can be set automatically or manually. The manual option is typically used with isolated networks.
Chapter 2 Prepare the Computer and Load Controller Firmware 3. Right-click Local Area Connection and choose Properties. 4. On the Networking tab, choose Internet Protocol Version 4 (TCP/IPv4) and click Properties.
Prepare the Computer and Load Controller Firmware Chapter 2 5. Select Use the following IP address and enter an IP address and Subnet mask for your computer. 6. Record the IP address and subnet mask. 7. Click OK. 8. Close the Local Area Connection Properties dialog box.
Chapter 2 Prepare the Computer and Load Controller Firmware Load the Controller Firmware IMPORTANT This section assumes that you downloaded the controller firmware from the Rockwell Automation technical support website to install on your CompactLogix 5370 L3 controller. If not, download the firmware before following the steps in this section. The firmware is available with Logix Designer application or you can download it from the support website. Go to http://www.rockwellautomation.
Prepare the Computer and Load Controller Firmware Chapter 2 4. Click Next. 5. Select the controller catalog number and click Next.
Chapter 2 Prepare the Computer and Load Controller Firmware 6. Expand the USB driver, and choose your controller. 7. Click OK. 8. Verify that your computer’s mode switch is in the REM position. RUN REM PROG 9. Choose the desired firmware revision and click Next. TIP 46 Consider the following: • If the Current Revision matches the firmware revision shown in the box below it, click Cancel. You are finished with this task. • This example uses firmware revision 21.001.23.
Prepare the Computer and Load Controller Firmware Chapter 2 10. To start the update of the controller, click Finish and then click Yes. Before the firmware upgrade begins, you see the following dialog box. Take the appropriate action for your application. In this example, the upgrade continues when OK is clicked. After the controller is updated, the status dialog box displays the message Update complete. 11. Click OK. 12. To close the ControlFLASH utility, click Cancel and then click Yes.
Chapter 2 Prepare the Computer and Load Controller Firmware Install Additional Software Depending on your application, you may need to install additional software. For example, if you are integrating a PanelView Plus terminal into your system, you must install the following: • RSLinx Enterprise software IMPORTANT • 48 You must install this software before you install any other additional software.
Chapter 3 Configure the EtherNet/IP Network In this chapter, you assign an IP address to your CompactLogix 5370 L3 controller. This quick start does not describe how to use other devices on the EtherNet/IP network. It is common, however, to use other devices on an EtherNet/IP network in a CompactLogix 5370 L1 control system. If you were to do so, for example, use a PanelView Plus terminal on an EtherNet/IP network, you need to assign an IP address to those devices.
Chapter 3 Configure the EtherNet/IP Network Before You Begin Before you begin, complete these tasks.
Configure the EtherNet/IP Network Chapter 3 What You Need Table 6 lists the software components you use in this chapter. Table 6 - What You Need to Configure the EtherNet/IP Network Component Description Studio 5000 environment Environment that combines engineering and design elements into a common environment. Logix Designer application Application used to create a project the CompactLogix 5370 L3 controller uses in your application.
Chapter 3 Configure the EtherNet/IP Network 2. From the Communications pulldown menu, choose RSWho. The RSWho dialog box appears. 3. Navigate to the USB connection. 4. Right-click the controller and choose Module Configuration. The Module Configuration dialog box appears. 5. Click the Port Configuration tab. 6. For Network Configuration Type, click Static to permanently assign this configuration to the port. IMPORTANT The controller’s default configuration is Dynamic.
Chapter 4 Configure the DeviceNet Network In this chapter, you configure the DeviceNet node address for the 1769-SDN module. You also create the RSNetWorx for DeviceNet file that stores network configuration. IMPORTANT Not all tasks described in this quick start are required to complete the final task, that is, use ladder logic to test a 1769-OB16 output module as described beginning on page 63. For example, you do not need a DeviceNet configuration file to test the module.
Chapter 4 • The tasks described in Chapter 2, Prepare the Computer and Load Controller Firmware on page 33, including: – – – – • Configure the DeviceNet Network Install the Studio 5000 environment and RSLinx Classic software Logix Designer application is installed when you install the Studio 5000 environment.
Configure the DeviceNet Network Chapter 4 Follow These Steps Apply Power to the DeviceNet Network 1606-X POWER L SUPPLY AC 120V AC 240V Input AC 100 -120/200 -240 N L Isolate powe r befo re disco page 56 Outpu V DC ok nnecting t 200W Lim DC 24V ited Pow er / 8A + – DC ok Set the 1769-SDN Module’s Node Address page 57 Create a DeviceNet Configuration File page 59 Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012 55
Chapter 4 Configure the DeviceNet Network Apply Power to the DeviceNet Network In this quick start, the CompactLogix 5370 L3 control system uses a 1606-XLDNET8 DeviceNet power supply to power the DeviceNet network. You completed the tasks described in Make a DeviceNet Network Connection (Optional) on page 29 to install the power supply and other components in the DeviceNet network, such as a KwikLink sealed terminator on each end of the KwikLink flat cable.
Configure the DeviceNet Network Chapter 4 Set the 1769-SDN Module’s Node Address 1. Start the software. 2. From the Tools pull-down menu, choose Node Commissioning. 3. Click Browse. When the Device Selection dialog box appears, you can browse to the 1769-SDN module over an EtherNet/IP network or USB connection. This example uses a USB connection.
Chapter 4 Configure the DeviceNet Network 4. Under the USB driver, expand the path to the 1769-SDN module as shown in the example graphic. 5. Click OK. 6. If you receive a linking device warning, click Yes. The Node Commissioning dialog box is populated with the 1769-SDN module’s current settings. 7. Enter a node address of 1 for the 1769-SDN module and click Apply. The Address is applied and is confirmed in the Messages box. 8. Record the node address.
Configure the DeviceNet Network Chapter 4 9. Click Close. Create a DeviceNet Configuration File 1. From the File pull-down menu, choose New. 2. Click Who Active to go online.
Chapter 4 Configure the DeviceNet Network 3. Expand the networks to the appropriate DeviceNet network. In this example, the network is Port 2, DeviceNet. 4. Record the following information about the 1769-SDN module: • • • Slot number = 2 • DeviceNet network node number = 1 Slot number in the CompactBus, 1769 Bus = 2 (this example) DeviceNet network node number = 1 (this example) 5. Click OK. 6. Click OK when the alert about uploading or downloading device information.
Configure the DeviceNet Network Chapter 4 7. Right-click the 1769-SDN module and choose Properties. 8. Click the Module tab. The information for your DeviceNet scanner module may vary from what is shown here. 9. Click Download. All configuration is cleared from the 1769-SDN scanner module, and the software is synchronized with the module.
Chapter 4 Configure the DeviceNet Network 10. From the Platform pull-down menu, choose CompactLogix. 11. Enter the slot number of the 1769-SDN module. 12. Click OK. 13. Save the file and record the file name and path. This quick start uses the example file name New DeviceNet.dnt. 14. Close RSNetWorx for DeviceNet software.
Chapter 5 Create a Logix Designer Project In this chapter you create a Logix Designer project. In the project you use ladder logic to create a push button that controls a light on a digital output module.
Chapter 5 Create a Logix Designer Project Before You Begin Before you begin, complete these tasks: • The tasks described in Chapter 1, Prepare the CompactLogix 5370 L3 Controller Hardware on page 17, including: – – – • Install the EtherNet/IP network Install the controller and the local expansion module Wire power to the controller The tasks described in Chapter 2, Prepare the Computer and Load Controller Firmware on page 33, including: – – – – Install the Studio 5000 environment and RSLinx Classic
Create a Logix Designer Project Chapter 5 Follow These Steps Create a Project page 66 Configure the Controller page 68 Add Local I/O Module page 70 Add the 1769-SDN to the Project page 71 Add Ladder Logic to Test the Local 1769-OB16 Module page 73 Download to the Controller and Test the Logic page 76 Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012 65
Chapter 5 Create a Logix Designer Project Create a Project 1. Start the application. 2. Click New Project. The New Project dialog box appears.
Create a Logix Designer Project Chapter 5 3. Choose your controller and name the project. 4. Click Next. 5. Choose a Security Authority and click Finish. For the purposes of this publication, we recommend that you choose No Protection, as shown.
Chapter 5 Create a Logix Designer Project Configure the Controller 1. Verify that your controller’s mode switch is in the REM position. RUN REM PROG 2. Click the RSWho button. 3. In the Who Active dialog box, expand the path to the controller and select it. 4. Click Go Online. 5. Click Download twice on successive dialog boxes. 6. Click Yes to change the controller mode to Remote Run.
Create a Logix Designer Project Chapter 5 7. Expand the I/O Configuration tree. 8. Right-click the controller and choose Properties. 9. Use the tabs on the Controller Properties dialog box to configure the controller. The IP address is set on the Internet Protocol tab. IMPORTANT Make sure you set an IP address and subnet Mask that matches the values set in Assign an IP Address to the Controller Over a USB Connection on page 51.
Chapter 5 Create a Logix Designer Project Add Local I/O Module 1. Right-click 1769 Bus and choose New Module. The Select Module Type dialog box appears. 2. If you have multiple I/O modules to add to the local bus, make sure the Close on Create checkbox is clear. If the checkbox is clear, the Select Module Type dialog box stays open after you choose and configure each I/O module. 3. Select the catalog number for the leftmost I/O module in the CompactLogix 5370 L3 controller system and click Create.
Create a Logix Designer Project Chapter 5 4. Use the tabs to create the parameters for the I/O module. IMPORTANT For the purposes of this exercise, make sure you change the Module Definition parameters so Electronic Keying is set to Disable Keying. 5. When the module configuration is complete, click OK. The module is added to the I/O Configuration. Add the 1769-SDN to the Project 1. Make sure the 1769-SDN DeviceNet scanner module is installed in the CompactLogix 5370 L3 controller system.
Chapter 5 Create a Logix Designer Project 3. Select the 1769-SDN scanner module and click Create. The Select Major Revision dialog box appears. 4. Select the Major Revision for your module and click OK. 5. When the New Module dialog box appears, configure the following parameters: • • • Name Slot Electronic Keying 6. Check the Open Module Properties checkbox and click OK. Additional tabs with configurable parameters appear.
Create a Logix Designer Project Chapter 5 7. On the RSNetWorx tab, click Browse to find the configuration (.dnt) file recorded. Use the configuration file name you saved. This quick start uses New DeviceNet.dnt. 8. Click OK. The module is added to the I/O Configuration. Add Ladder Logic to Test the Local 1769-OB16 Module 1. Expand the Tasks folders. 2. Right-click MainRoutine and choose Open. A blank MainRoutine opens. 3.
Chapter 5 Create a Logix Designer Project 4. Double-click the ? in the Examine On element. 5. Type PB (for push button). 6. Press Enter. 7. Right-click PB and choose New ‘PB’. 8. Keep the default settings and click one of the Create options.
Create a Logix Designer Project Chapter 5 9. Double-click the ? in the Output Energize element. 10. Name the Output Energize element OB16_Light. IMPORTANT Do not use spaces in the tag name. Use underscores (_) instead. 11. Press Enter. 12. Right-click the OB16_Light element name and choose New “OB16_Light”. OB16_Light is an alias tag for the I/O point tag name. With an alias tag, you can assign a simple name to a physical I/O point address. 13. From the Type pull-down menu, choose Alias. 14.
Chapter 5 Create a Logix Designer Project 16. The graphic shows the Output Energize after assigning the Alias tag to a point on the output module. 17. Save your changes. Download to the Controller and Test the Logic 1. From the mode pull-down menu, choose Download. 2. When the dialog box appears with information about the download, click Download. 3. Click Yes to change the controller mode to Remote Run. 4. Move the mode switch on your controller to RUN.
Create a Logix Designer Project Chapter 5 5. Select the PB Examine On instruction. 6. Press Ctrl+T to toggle the state from 0 to 1, or Off to On. 7. Verify that the status indicator on the digital output module turns on after you toggle the state to 1 or On. 8. Press Ctrl+T to toggle the state back to 0 or Off. 9. Save the project and go Offline.
Chapter 5 Create a Logix Designer Project Notes: 78 Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012
Appendix A Understanding Other Application Options This chapter describes two application options available with a CompactLogix 5370 L3 controller.
Appendix A Understanding Other Application Options DLR Network Topology A DLR network topology is a single-fault-tolerant ring network in which DLR-capable Allen-Bradley devices use embedded technology and dual EtherNet/IP ports to establish a network that is resilient to single points of failure, recovers faster when single faults occur, and does not require switches.
Understanding Other Application Options Appendix A Follow These Steps Begin Physical Device Installation Create a Logx Designer Project Complete Physical Device Installation Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012 81
Appendix A Understanding Other Application Options Integrated Motion on the EtherNet/IP Network Integrated Motion on the EtherNet/IP network is an integrated motion solution on a standard, unmodified EtherNet/IP network that delivers high performance with lower costs and simpler design or configuration when compared to traditional, multi-network motion applications.
Index Numerics 1769 Compact I/O power supplies wire 32 H hardware 10, 15, 18 connections to other devices 4 optional system devices 12 C CompactLogix 5370 L3 controllers available 10 devices to integrate 12 features 10 ControlFLASH software 14, 34 install 38 load firmware 44-47 controller firmware load 44 I I/O support 70 Integrated Motion on the EtherNet/IP network 79, 82 internal energy storage solution 10 K Kinetix 350 drives 12 D DeviceNet network 10, 53 connection 29 devices Kinetix 350 drives 12
Index power supplies wire 32 PowerFlex 40 drives 12 PowerFlex 70 drives 12 R required parts 15 RSLinx Classic software 14, 34, 51 RSNetWorx for DeviceNet software 14, 34 software ControlFLASH 14 load firmware 44-47 install ControlFLASH 38 install the Studio 5000 environment 36 Logix Designer application 14, 34, 51, 63 required 14 RSLinx Classic 14, 34, 51 RSNetWorx for DeviceNet 14, 34 Studio 5000 environment install 36 U S SD card 10 installation 21 84 USB connection 27 Rockwell Automation Publicat
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.