Quick Start Owner's manual

30 Rockwell Automation Publication IASIMP-QS025B-EN-P - December 2012
Chapter 1 Prepare the CompactLogix 5370 L2 Controller Hardware
Wire the DeviceNet Network Power Supply
1. Use the information in the following table to connect incoming power to the network
power supply.
2. Place the switch in the position that matches your supply voltage.
3. Use the information in the followingtable to connect the DeviceNet power tap to the
power supply.
4. Connect the DeviceNet power tap to the DeviceNet network.
5. Power the 1606- XLDNET4 standard switched-mode power supply connected to the
CompactLogix 5370 L2 controller, as described in Connect Power to the Controller on
page 25.
WARNING: Verify that all incoming power is turned off before wiring power.
Connect To
V AC COM N (neutral)
120/240V AC L (line)
Ground
Connect To
Red +
White N/A
Shield N/A
Blue N/A
Black
ATTENTION: If you have unused DeviceNet wires, make sure they do not come into contact with the other wires.