User guide

Compact I/O Thermocouple/mV Input Module 19
Publication 1769-IN026C-EN-P - February 2010
Configuration Data File
To select Make these bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Filter Frequency
10 Hz
Not Used
(1)
(1)
An attempt to write any non-valid (not used or spare bits) bit configuration into any selection field results in a module
configuration error.
1 1 0
60 Hz 0 0 0
50 Hz 0 0 1
250Hz 0 1 1
500 Hz 1 0 0
1 kHz 1 0 1
Open-circuit
Upscale 0 0
Downscale 0 1
Hold Last State 1 0
Zero 1 1
Temp. Units
°C 0
°F 1
Input Type
Thermocouple J 0 0 0 0
Thermocouple K 0 0 0 1
Thermocouple T 0 0 1 0
Thermocouple E 0 0 1 1
Thermocouple R 0 1 0 0
Thermocouple S 0 1 0 1
Thermocouple B 0 1 1 0
Thermocouple N 0 1 1 1
Thermocouple C 1 0 0 0
-50…50 mV 1 0 0 1
-100…100 mV 1 0 1 0
Data Format
Raw/Proportional Data 0 0 0
Engineering Units 0 0 1
Engineering Units x 10 1 0 0
Scaled-for-PID 0 1 0
Percent Range 0 1 1
Enable Channel
Disabled 0
Enabled 1
TIP
Program defaults are indicated by 0 values. For example, type J thermocouple is the
default (no user intervention) thermocouple type.