User Manual

80 Rockwell Automation Publication 1769-UM004B-EN-P - March 2010
Chapter 5 Diagnostics and Troubleshooting
Error Codes
This table explains the extended error code.
Table 11 - Extended Error Codes
Error Type Hex
Equivalent
(1)
Module
Error Code
Extended Error
Information
Code
Error Description
Binary Binary
No error X000 000 0 0000 0000 No error
General common
hardware error
X200 001 0 0000 0000 General hardware error; no additional information
X201 001 0 0000 0001 Power-up reset state
Hardware-specific
error
X300 001 1 0000 0000 General hardware error; no additional information
X301 001 1 0000 0001 Microprocessor hardware error; hardware ROM error
X302 001 1 0000 0010 Hardware EEPROM error
X303 001 1 0000 0011 Channel 0 calibration error
X304 001 1 0000 0100 Channel 1 calibration error
X305 001 1 0000 0101 Channel 2 calibration error
X306 001 1 0000 0110 Channel 3 calibration error
X307 001 1 0000 0111 Channel 4 calibration error
X308 001 1 0000 1000 Channel 5 calibration error
X309 001 1 0000 1001 CJC0 calibration error
X30A 001 1 0000 1010 CJC1 calibration error
X30B 001 1 0000 1011 Channel 0 analog/digital converter error
X30C 001 1 0000 1100 Channel 1 analog/digital converter error
X30D 001 1 0000 1101 Channel 2 analog/digital converter error
X30E 001 1 0000 1110 Channel 3 analog/digital converter error
X30F 001 1 0000 1111 Channel 4 analog/digital converter error
X310 001 1 0001 0000 Channel 5 analog/digital converter error
X311 001 1 0001 0001 CJC0 analog/digital converter error
X312 001 1 0001 0010 CJC1 analog/digital converter error